MICS / MICS-N
17
English 07/07
HYDRAULIC DATA
Minimum water content MICS
Litri
55
69
96
118
135
Minimum water content MICS-N
Litri
71
91
118
150
168
1
2
0
2
4
6
8
10
12
14
16
50
75
100
125
150
175
200
225
250
275
300
325
350
3
4
Model
0072
0092
0122
0152
0182
(1)
MICS/MICS-N 0072
(2)
MICS/MICS-N 0092 MICS 0122
(3)
MICS-N 0122 MICS 0152
(4)
MICS-N 0152 MICS/MICS-N 0182
USEFUL PUMP HEAD CURVES (*)
(*) To obtain the useful head of the installation, subtract the pressure drop of the plate heat exchanger
MINIMUM WATER CONTENT
I
A
Model
Water
m
3
/h
3,0
3,1
4,0
5,5
6,8
7,7
8,0
flow
l/sec
0,83
0,86
1,11
1,53
1,89
2,14
2,22
HEAT EXCHANGER PRESSURE DROP (WATER SIDE)
Note: the values highlighted refer to the rated flow
evaporator water in/out IN/OUT
7/12° C
condenser air in
35°
0072
kPa
32
34
-
-
-
-
-
0092
Pressure
kPa
-
21
35
-
-
-
-
0122
drop
kPa
-
14
22
42
64
82
-
0152
kPa
-
-
17
31
48
62
66
0182
kPa
-
-
-
24
37
48
52