24
WALL-MOUNTED CONTROLS
User
Function selector
Cooling
Riscaldamento
Off
Fan selector
Maximum fan speed
Medium fan speed
Minimum fan speed
NSW wall-mounted control
The NSW control is used to regulate the air (3 speeds), the temperature through electronic thermostat, to select the sum-
mer/winter mode of operation and to switch the fan coil on/off and hot start function by minimun thermostat kit.
Technical data
Supply voltage
230 V ~ ±10%
Supply frequency
50/60 Hz
Contact rating
2,5 A (cosØ ≥0.85; 230V)
Storage temperature
-20 °C / +85 °C
Max. storage humidity
90% (not condensing)
Working temperature
0 °C / +55 °C
Max. working humidity
90% (not condensing)
Protection rating
IP 30
Case material
PC+ABS (flame retardant V0)
Color
RAL 9003 (white)
Dimensions
120 x 75 x 25 mm
Weight
0,185 kg