Minimum system water content
Size
0021M-T
0025M-T
0031M-T
0041M-T
0051T
0061T
Minimum water content BRA2
l
18
21
24
31
36
44
Minimum water content BRN2
l
25
35
40
50
55
65
Expansion vessel size
Size
0021M-T
0025M-T
0031M-T
0041M-T
0051T
0061T
Expansion vessel BRA2
l
2
2
2
2
2
2
Expansion vessel BRN2
l
2
2
2
2
2
5
Safety valve calibration
Size
0021M-T
0025M-T
0031M-T
0041M-T
0051T
0061T
Safety valve
l
6
6
6
6
6
6
FACTORY CONNECTED
INSTALLER CONNECTIONS
UTILITY
RETURN
UTILITY
OUTLET
12
12
14
14
2
10
2
4
3
5
11
6
1
15
15
7
15
8
12
13
System water circuit connection diagram, BRA2 version WITHOUT HYDRONIC KIT
1 PRESSURE
GAUGE
2 VIBRATION-ISOLATING
JOINT
3 SHUT-OFF
VALVE
4 CALIBRATING
VALVE
5 FLOW
SWITCH
6 THERMOMETER
7 CIRCULATOR
PUMP
8 SAFETY
VALVE
9 EXPANSION
VESSEL
10 MESH
FILTER
11 FILL/TOP-UP
12 TEMPERATURE
PROBE
13 DIFFERENTIAL
PRESSURE
SWITCH
14 DRAIN/CHEMICAL
WASHING
VALVE
15 SYSTEM
VENT
FACTORY CONNECTED
INSTALLER CONNECTIONS
UTILITY
RETURN
UTILITY
OUTLET
12
12
9
15
8
14
14
2
10
2
4
3
5
11
6
1
15
15
7
13
System water circuit connection diagram, BRA2 version WITHOUT HYDRONIC KIT
1 PRESSURE
GAUGE
2 VIBRATION-ISOLATING
JOINT
3 SHUT-OFF
VALVE
4 CALIBRATING
VALVE
5 FLOW
SWITCH
6 THERMOMETER
7 CIRCULATOR
PUMP
8 SAFETY
VALVE
9 EXPANSION
VESSEL
10 MESH
FILTER
11 FILL/TOP-UP
12 TEMPERATURE
PROBE
13 DIFFERENTIAL
PRESSURE
SWITCH
14 DRAIN/CHEMICAL
WASHING
VALVE
15 SYSTEM
VENT
UTILITY
RETURN
UTILITY
OUTLET
FACTORY CONNECTED
INSTALLER CONNECTIONS
12
12
15
12
13
14
10
2
4
11
1
15
14
2
3
5
6
15
7
8
System water circuit connection diagram, BRN2 version WITH HYDRONIC KIT
1 PRESSURE
GAUGE
2 VIBRATION-ISOLATING
JOINT
3 SHUT-OFF
VALVE
4 CALIBRATING
VALVE
5 FLOW
SWITCH
6 THERMOMETER
7 CIRCULATOR
PUMP
8 SAFETY
VALVE
9 EXPANSION
VESSEL
10 MESH
FILTER
11 FILL/TOP-UP
12 TEMPERATURE
PROBE
13 DIFFERENTIAL
PRESSURE
SWITCH
14 DRAIN/CHEMICAL
WASHING
VALVE
15 SYSTEM
VENT