English 05/09
ACCURATE AX - AW - AD - AT - AF
49
CALIBRATING THE CONTROL AND SAFETY DEVICES
A
I
U
After starting the air-conditioner, make the following adjustments
- Room temperature (cooling and heating set point).
- Relative humidity (set point for humidification and dehumidifi-
cation);
- Dirty filter differential pressure switch: see the paragraph on
"CALIBRATING THE DIRTY FILTER SENSOR".
The calibration values of the control and safety devices must not
be altered.
Symbol
Description
F1
High pressure switch
F2
Low pressure switch
TH1
Safety thermostat (versions T and H)
Symbol Activation
Differential Reset
F1
28 bar (opening)
-
Manual reset
F2
1,5 bar (opening)
1.5 bar
2.5 bar (automatic)
TH1
320 °C (opening)
-
Manual reset