ACCURATE AX - AW - AD - AT - AF
OPERATING LIMITS
A
I
U
All versions.
The DX units are designed for operation within
the following operating ranges (the limits are considered for new
units that have been correctly installed and maintained):
Environmental conditions
from 18.0°C, 45% RH at 30.0°C, 55% RH
Outside conditions
from +10.0°C to +46.0°C in STANDARD version without con-
densing control
from -20.0°C to +46.0°C in MODULATING version with con-
densing control
from -45.0°C to +46.0°C in the LT version (low temperature).
For the correct operation of the air-conditioner, the conditions
shown in the following graph must be observed:
18° C/45% ROOM TEMPERATURE
30°C/55%t
-20 °C
-45 °C
46 °C
t
Exter
n
al Te
m
perat
u
re °C
35
°
C
standard version
LT version (low temperature)
OPERATING ZONE
28°C
OPTIONAL BASE MOULDING (OVER UNITS)
A
I
U
The "OVER" units are designed for the connections to pass
through the base of the unit; nonetheless, if there is no raised
floor (units with intake from the rear or front),
to simplify the
connection of the pipes and cables, a base moulding must
be used.
The base moulding, available as an accessory, is epoxy-polyester
powder painted, in the same colour as the external panels on the
air-conditioner, measures 200 mm in height and is fitted with an
inspection panel at the front fastened by two latches tightened
1/4 of a turn.
The inside walls are lined with soundproofing material.
On the right- and left-hand sides of the base moulding are six
pre-cut sections for passing the cables and pipes;
The moulding must be fastened to the air-conditioner using the
M6 threaded inserts already arranged on the base.
For the OVER units with intake from the bottom, base mouldings
are available with a height of 500 mm.
In this case too, the air-conditioner must be screwed to the base
moulding during the positioning phase.
C1
A1
200
air-co
n
ditio
n
er base
un
it
m
o
u
ldi
ng
C1
A1
450
Access to the i
n
let/o
u
tlet
co
nn
ectio
n
s
f
ro
m
the rear
A1 mm
600
1000
980
1530
2080
2630
C1 mm
485
485
770
770
770
770
07
10
15
18
20
26
29
39
30
40
50
55
60
70
80
90