background image

10

OUTDOOR UNIT MINIMUM SPACE 

REQUIREMENTS

If there are obstacles around the unit two sides must be open 

for proper operation

 

12" fr

om wall

20" above

12" on left

79" in fr

ont

24" on right

 

Figure 6: Minimum space requirements for outdoor unit

OBSTACLE ABOVE UNIT: 

If there is an obstacle above the 

unit maintain 20 in of space 

from the top of the unit.

 

Figure 7: Minimum space for 

obstacle on top of unit

INSTALLATION 

OF OUTDOOR UNIT

CHOOSE A LOCATION 

Before installing the outdoor unit, you must choose an appropriate 

location. The following are standards that will help you choose an 

appropriate location for the unit:
• 

Meets all spatial requirements shown in figure 6 below.

•  Good air circulation and ventilation.
•  Firm and solid—the location can support the unit and will not 

vibrate.

•  Noise from the unit will not disturb others.
•  Protected from prolonged periods of direct sunlight or rain.

CHOOSING BASE PAD FOR UNIT

Condenser must be placed securely on a level foundation. The base 

can be made out of fiberglass material, stepping stones or pour a 

concrete pad. Make sure the unit can bolt into the base material to 

secure it properly. Gravel or sand under the base can keep the base 

more secure and assist with keeping the unit level. 

EXTREME WEATHER CONSIDERATIONS: 

If the unit is exposed to heavy wind: Install unit so that air outlet 

fan is at a 90° angle to the direction of the wind. If needed, build a 

barrier in front of the unit to protect it from extremely heavy winds. 
If the unit is frequently exposed to heavy rain or snow: Build a 

shelter above the unit it to protect it from the rain or snow. Be 

careful not to obstruct air flow around the unit.

IF THE UNIT IS SURROUNDED ON THREE SIDES: 

Make sure each side of the unit has 12 in clearance and at least 

8 in of clearance from wall. Make sure the fan at the front is not 

blocked.  

12' from left

12' from right

8' from back

 

Figure 8: Minimum space for 3 sides 

WHEN THERE IS AN OBSTACLE ONLY IN 

FRONT OF THE UNIT:

 

If there is an obstacle only in front of the unit maintain at least 

20 in of space from the fan to that obstacle. 

20" from fan

 

 

Figure 9: Minimum space obstacle in front of unit 

SPACE FOR MAINTENANCE:

 

Always maintain a 20 in by 20 in space in front of the main 

panel on the unit for maintenance access. 

20"

20"

 

 

Figure 10: Minimum space for maintenance 

MINIMUM SPACE FOR TWO UNITS: 

If you have two outdoor units next to one another maintain a 

separation of 12" from the side of each. Do not place units with 

fans pointing at one another.

12" between units

Figure 11: Minimum space for two units

20" Minimum

Summary of Contents for easyair CR12000SACH

Page 1: ...ORE ASSEMBLY AND USE Read and follow all safety rules and instructions before operating this equipment THIS PRODUCT IS INTENDED FOR HOUSEHOLD USE ONLY Please keep this manual for future reference OWNER S MANUAL INSTALLATION GUIDE Install without the need for an HVAC technician Do it y urself easyair ...

Page 2: ...EMA 5 15 Control Panel Temperature Display Only operates with remote Remote Control Infrared Remote Compressor Rotary Thermostat Digital Refrigerant R410a 800g Line Set is Pre charged Filter Included washable Noise Interior Unit 42 dB Exterior Unit 53 dB Capacity Cooling BTU 12 000 Dehumidification pts hour 1 25 Heating BTU 14 000 heat pump Approximate Max Enclosure Size 500 550 sq ft Well insulat...

Page 3: ...he plug for this unit is polarized with one blade wider than the other Do not force the plug into an electrical outlet Do not alter the plug in any way If the plug does not fit into the outlet reverse the plug If it still does not fit contact a qualified technician to install a proper outlet Do not use if the power cord is damaged or the connection to the wall outlet is loose Operate product only ...

Page 4: ... in the affected room It can cool and dehumidify the air completely automatically and also provide heat using a heat pump Air pulled by the fan enters through the grill of the front panel and passes through the filter which traps dust inside Air is then sent to the heat exchanger and is cooled dehumidified or re heated by the heat exchanger Heat removed from the air is then sent outside When the c...

Page 5: ...nction in SLEEP mode which will automatically adjust the temperature to maximize comfort during night time sleep To put the air conditioner into SLEEP mode press the SLEEP button on the remote until the symbol is pointing to SLEEP on the remote s display If the system is set to run using the cooling or dry modes the set temperature will automatically be raised by 1 degree every 60 minutes for a to...

Page 6: ...6 REMOTE CONTROLLER BUTTON DIAGRAM Turns off digital display on indoor unit LAMP button Indicates the selected air rate It works on three dimensional air flow model ...

Page 7: ...it by inserting attaching vibration proof pads between the unit and fittings Avoid leaving items near the outlet and inlet of the outdoor unit These can cause malfunction or increase operation noise Contact ClimateRight Customer Service if you hear irregular sounds during operation Only use a soft dry cloth to wipe the unit clean If the unit is especially dirty you can use a cloth soaked in warm w...

Page 8: ...ommodate piping to both the left and right See figure 2 below for different ways piping can be fixed Figure 3 provides measurements for hole placement for Rear Outlet and Left Rear Outlet configurations Make sure to use minimum 2 75 hole saw Figure 3 Rear and left rear hole placement measurements Indoor wall mount 2 5 2 5 1 5 1 5 2 75 2 75 Rear outlet Recommended Left Rear outlet Figure 2 Optional...

Page 9: ...extension to the end of drain hose before operating Wrap the extension connection point firmly with Teflon tape to ensure a good seal and to prevent leaks INCORRECT CORRECT Figure 5 Installation of drain hose 7 Carefully bend the line set downward routing them to either the left or right as needed to connect to the condenser portion of the unit outside 8 Click the 2 round plastic housings around t...

Page 10: ...e more secure and assist with keeping the unit level EXTREME WEATHER CONSIDERATIONS If the unit is exposed to heavy wind Install unit so that air outlet fan is at a 90 angle to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds If the unit is frequently exposed to heavy rain or snow Build a shelter above the unit it to protect it from ...

Page 11: ...d Gravel or sand under the base can keep the base more secure and assist with keeping the unit level Unit must be 12 away from the wall for proper airflow and servicing 10 WARNING Read all safety instructions on page 3 before installing outdoor unit Read all outdoor installation requirements DO NOT DO NOT install near an obstacle that will block air inlets and outlets DO NOT install near a public ...

Page 12: ... unit current 6 If connecting power to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1 8in 3mm must be incorporated in the fixed wiring Use an approved circuit breaker or switch 7 Only connect the unit to an individual branch circuit outlet Do no connect another appliance to that outlet 8 Make sure to properly ground the air conditione...

Page 13: ...lide the spade connector on the end of the black L1 wire into the L1 terminal and tighten Then slide the spade connector on the end of the white L2 wire into the L2 terminal and tighten 16 Route utility power cord and line set power cord through the strain relief and tighten with screw removed in Step 18 17 Reinstall panel on unit and tighten screw FINISH INSTALLATION 18 Once the condenser is secu...

Page 14: ...m remote controller 5 Cover both indoor and outdoor units to prevent dust buildup PRE SEASON INSPECTION 1 Check for damaged wires 2 Clean air filters 3 Check for leaks 4 Replace batteries in the remote controller 5 Make sure nothing is blocking all air inlets and outlets TROUBLESHOOTING WARNING If ANY of the following conditions occurs turn off your unit immediately The power cord is damaged or ab...

Page 15: ...nd during operation This is normal and is caused by refrigerant gas flowing through both indoor and outdoor units Low hissing sound when the system starts has just stopped running or is defrosting This noise is normal and is caused by the refrigerant gas stopping or changing direction Squeaking sound Normal expansion and contraction of plastic and metal parts caused by temperature changes during o...

Page 16: ...ods winds fires lightning accidents corrosive environments rust etc or other conditions beyond the control of the Company 6 Parts not supplied or designated by Company or damages resulting from their use 7 Products installed outside USA and Canada 8 Electricity or fuel costs or increases in electricity or fuel costs from any reason whatsoever including additional or unusual use of supplemental ele...

Page 17: ..._________________________________________ Date of Purchase___________________________________ Date of Installation__________________________________ Owners Name______________________________________ Address of Installation_______________________________ _______________________________ Installing Contractor_________________________________ Address_________________________________________ Phone No E...

Reviews: