LCDI POWER CORD AND PLUG
This air conditioner is equipped with an LCDI (Leakage Current Detection and
Interruption) power cord and plug as required by US National Electric Code 440.65.
This cord consists of a length of shielded flexible cord with no termination on the load
side and a LCDI attachment plug on the line side.
The LCDI power cord and plug will remove the supply source via electrical disconnect
(circuit trip) if the nominal current leakage between the cord shield and either load
conductor exceeds a predetermined value. The cord will remain de-energized until
the devise has been manually reset. This is intended to reduce the risk of a fire in the
power cord or combustible materials nearby. The cord shields are not grounded and
they must be considered a shock hazards if exposed. The cord shield must not be
connected to ground or to any exposed metal.
The test and reset buttons on the LCDI Plug are used to check if the plug is
functioning properly. To test:
1. Plug power cord into wall outlet
2. Press TEST Button, circuit should trip, cutting power to the air conditioner
3. Press RESET button for use
If test button is pressed and unit can still be turned on, current leakage has been
detected. Do not use the air conditioner or attempt to reset the LCDI Plug. Contact
ClimateRight
®
Customer Service for troubleshooting recommendations.
WARNING:
1. DO NOT press the TEST button while the air conditioner is operating.
2. The TEST and RESET buttons should not be used as “ON” and “OFF” switches.
3. The cord and plug are not intended to offer protection to externally connected
loads or supply circuits.
4. The cord and plug are intended for indoor use only.
PARTS AND ASSEMBLY
3
4
EXHAUST HOSES
WINDOW KIT
ASSEMBLY & INSTALLATION
INSTALLATION
When the unit is operating as an air conditioner, heater, or dehumidifier, the unit
draws in fresh outdoor air and exhausts hot air (in AC or dehumidifier mode) or
cool air (in Heat mode) out of the room to complete the air exchange. When the
unit is operating in fan mode, no outdoor air exchange takes place. The window kit
and exhaust hose do not need to be installed when the unit is used as a fan.
NOTE: The supplied window kit can be installed in sliding windows and sliding
glass doors up to 8 ft. long (approximate length).
MOUNTING THE EXHAUST HOSES
• Choose a suitable location, near a grounded electrical outlet and suitable window
or door. Remove packaging and locate components.
• Extend both ends of the exhaust hoses approximately 6 inches.
• Screw the window kit adapter onto one end of the exhaust hose clockwise.
• Screw the hose adapter onto the other end of the exhaust hose clockwise.
Repeat on the other exhaust hose.
• Remove outlet covers from the back of the unit by screwing them
counter-clockwise, then lifting up.
• Mount the exhaust hoses onto the back of the unit by locking the hose adapters
into place.
RESET
TEST