Troubleshooting (Cont.)
Code
Fault
Mode
Possible Cause
Solution
10
ECM Low RPM
ALL
Blower does not operate
Check blower line voltage
ALL
Blower does not operate
Check blower low voltage wiring
ALL
Blower operating
with incorrect airflow
Wrong unit size selected - check unit configuration
ALL
Blower operating with
incorrect airflow
Wrong unit family selected - check unit configuration
ALL
Blower operating
with incorrect airflow
Incorrect motor size
ALL
Blower operating
with incorrect airflow
Incorrect blower selection
11
Low Air Coil Pressure
CL
Low Return Air temp
Bring air temp within design parameters
CL
Plugged air filter
Clean or replace air filter
CL
Bad Suction Pressure
Transducer
If supply voltage at BLK and GND wires reads 4.5-5.5 VDC but signal
at GND and RED is not between 0.5-4.5 VDC, replace sensor
CL
Insufficient charge
Check for refrigerant leaks
12
Control Fault
ANY
EXM not properly programmed reprogram EXM using Service Tool
ANY
Bad EXM
replace EXM
13
Low Pump Flow
ALL
Flat loop
Flush and repressurize loop.
ALL
Air pocket
Flush and repressurize loop.
ALL
System setup for single and
not parallel pumping.
Change unit loop pump configuration.
ALL
Pump Failure
Check pump.
ALL
Bad Flow Sensor
Check flow sensor.
14
High Discharge temp
ALL
Insufficient charge
Check for refrigerant leaks
HT
Water temp out of range
Bring water temp within design parameters
CL
Air temp out of range
Bring air temp within design parameters
ALL
Faulty EEV
Check EEV operation, superheat will be high as well
ALL
Fouled heat exchanger
Clean appropiate coil
15
Discharge Pressure Sensor
ALL
Bad tranducer
If supply voltage at BLK and GND wires reads 4.5-5.5 VDC but signal
at GND and RED is not between 0.5-4.5 VDC, replace sensor
ALL
Bad wiring harness
Check harness
ALL
Bad EXM
If supply voltage across BLK and GND doesn’t read 4.5-5.5 VDC
replace EXM
ALL
Bad EXM
If voltage across GND and RED reads between 0.5-4.5 VDC but fault
still exists, replace EXM
16
Suction Pressure Sensor
ALL
Bad tranducer
If supply voltage at BLK and GND wires reads 4.5-5.5 VDC but signal
at GND and BLU is not between 0.5-4.5 VDC, replace sensor
ALL
Bad wiring harness
Check harness
ALL
Bad EXM
If supply voltage across BLK and GND doesn’t read 4.5-5.5 VDC
replace EXM
ALL
Bad EXM
If voltage across GND and BLU reads between 0.5-4.5 VDC but fault
still exists, replace EXM
17
Space temp Sensor
ALL
Bad thermostat
Check thermostat to ensure that it is operating
ALL
Bad EXM
Use T-Stat service mode to check other temp values as well as space
humidity. If not, replace EXM
ALL
Bad wiring
Check wiring between the thermostat and EXM
ALL
Incorrect master/slave setting
Check that DIP switch 1 is set to the ON position
18
Space Humidity Sensor
ALL
Bad thermostat
Check thermostat to ensure that it is operating
ALL
Bad EXM
Use T-Stat service mode to check other temp values as well as space
temp. If not, replace EXM
ALL
Bad wiring
Check wiring between the thermostat and EXM
ALL
Incorrect master/slave setting
Check that DIP switch 1 is set to the ON position