Table 7b: DXM2 LED and Alarm Relay Operations
DXM2 Controls
Description
of Operation
Status LED
(Red)
Status LED
(Green)
Alarm Relay
DXM2 is
non-functional
Off
Off
Open
Normal Mode
On
On
Open
Normal Mode -
Communicating
On
Very Slow
Flash
Open
Normal Mode with
UPS Warning
On
On
Cycle (closed 5
sec., Open 25 sec.)
Normal Mode -
HWG pump active
Slow Flash
-
Open
Fault Retry
-
Slow Flash
Open
Lockout
-
Fast Flash
Closed
Active Over/Under
Voltage Condition
-
Slow Flash
Open (Closed after
15 minutes)
Night Setback
Flashing Code 2
-
-
ESD
Flashing Code 3
-
-
Invalid T-stat Inputs
Flashing Code 4
-
-
High Temperature
HWG Lockout
Flashing Code 5
-
-
HWG Temperature
Sensor Fault
Flashing Code 6
-
-
Test Mode
Fast Flash
-
-
Test Mode -
ECM blower active
Flashing Code
per 100 CFM
-
-
Test Mode -
No fault in memory
-
Flashing
Code 1
Cycling Code 1
Test Mode - HP/HPWS
fault in memory
-
Flashing
Code 2
Cycling Code 2
Test Mode -
LP fault in memory
-
Flashing
Code 3
Cycling Code 3
Test Mode -
LT1 fault in memory
-
Flashing
Code 4
Cycling Code 4
Test Mode -
LT2 fault in memory
-
Flashing
Code 5
Cycling Code 5
Test Mode -
CO fault in memory
-
Flashing
Code 6
Cycling Code 6
Test Mode - Over/Un-
der voltage in memory
-
Flashing
Code 7
Cycling Code 7
Test Mode - UPS warn-
ing in memory
-
Flashing
Code 8
Cycling Code 8
Test Mode - Swapped
thermistor in memory
-
Flashing
Code 9
Cycling Code 9
Test Mode - Air
fl
ow
fault in memory
-
Flashing
Code 10
Cycling Code 10
Test Mode - IFC Fault
in Memory
-
Flashing
Code 13
Cycling Code 13
-Fast Flash = 2
fl
ashes every 1 second
-Slow Flash = 1
fl
ash every 2 seconds
-Very Slow Flash = 1
fl
ash every 5 seconds
-Flash code 2 = 2 on pulses, 10 second pause, 2 on pulses, 10
second pause, etc.
-On pulse 1/3 second; off pulse 1/3 second