Tranquility Aluminum Tube Cased Coil (TAC) 

R e v. :   A u g u s t   2 1 ,   2 0 1 8

c l i m a t e m a s t e r. c o m

Installation

•  Make provisions for disconnecting and cleaning of the 

primary drain line should it become necessary. Install 

condensate trap at each unit with the top of the trap 

positioned below the unit condensate drain connection 

as shown in Figure 7.  Design the depth of the trap 

(water-seal) based upon the amount of ESP capability 

of the blower (where 2 inches [51mm] of ESP capability 

requires 2 inches [51mm] of trap depth). As a general 

rule, 1-1/2 inch [38mm] trap depth is the minimum.

•  Always vent the condensate line when dirt or air 

can collect in the line or a long horizontal drain line 

is required. Also vent when large units are working 

against higher external static pressure than other units 

connected to the same condensate main since this may 

cause poor drainage for all units on the line. WHEN A 

VENT IS INSTALLED IN THE DRAIN LINE, IT MUST 

BE LOCATED AFTER THE TRAP IN THE DIRECTION 

OF THE CONDENSATE FLOW.

•  Auxiliary drain line should be run to a place where it will 

be noticeable if it becomes operational. Occupant should 

be warned that a problem exists if water should begin 

running from the auxiliary drain line.

•  Plug the unused drain connection with the plugs 

provided in the parts bag, using a thin layer of Teflon 

paste, silicone or Teflon tape to form a water tight seal.

•  Test condensate drain pan and drain line after installation 

is complete. Pour water into drain pan, enough to fill 

drain trap and line. Check to make sure drain pan is 

draining completely, no leaks are found in drain line 

fittings, and water is draining from the termination of the 

primary drain line.

Charging the System

See Compressor Section IOM for charging information.

� 

CAUTION! 

CAUTION!

 It is recommended that an auxiliary/secondary 

drain pan be installed under units containing evaporator 

coils that are located in any area of a structure where

damage to the building or building contents may occur as 

a result of an overflow of the coil drain pan or a stoppage 

in the primary condensate drain piping.

FIGURE 7

FIELD-INSTALLED DUCT FLANGES

Figure 7: Condensate drain trap/vent

Figure 8: Field-installed duct flanges

Duct Flanges

Field-installed duct flanges (4 pieces) are shipped with units. 

Install duct flanges as needed on top or bottom of the coil 

casing. (See Figure 8.)

2”

1.5”

1.5”

1/8” Per 

Foot

UNIT MUST BE LEVEL OR SLIGHTLY 

PITCHED TOWARD DRAIN CONNECTION

[5 cm]

[3.8 cm]

[3.8 cm]

[11mm per m]

Summary of Contents for Tranquility TAC026BM17S

Page 1: ...tenance Instructions 97B0100N01 Rev August 21 2018 Tranquility Aluminum Tube Cased Coil TAC Table of Contents Model Nomenclature 3 General Information 4 Safety Inspection 5 Specifications 6 Dimensions...

Page 2: ...This page was intentionally left blank...

Page 3: ...ture AC T B 026 2 3 1 4 5 6 7 T TRANQUILITY HFC 410A MODEL TYPE AC CASED COIL CONFIGURATION 026 NOMINAL CAPACITY 038 049 REVISION LEVEL 064 M 8 COIL OPTIONS M MULTI POSITION CASED COIL S 11 FUTURE USE...

Page 4: ...r to file all necessary claims with the carrier Notify your equipment supplier of all damage within fifteen 15 days of shipment Storage Equipment should be stored in its original packaging in a clean...

Page 5: ...ion which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation or an unsafe practice which if not avoided could result in minor or moderate injury...

Page 6: ...0 42 17 5 44 5 0 120 0 157 0 199 0 246 TAC026BM21S 5 70 0 53 21 53 3 0 113 0 145 0 181 0 222 TAC038BM21S 8 55 0 79 0 062 0 086 0 112 0 140 0 170 0 202 0 236 TAC038BM24S 8 55 0 79 0 062 0 086 0 112 0...

Page 7: ...ZONTAL PRIMARY DRA N I SUCTION LINE LIQUID LINE SECONDARY DRAIN NOTE FLANGES ARE PROVIDED FOR FIELD INSTALLATION SECONDARY DRAIN 3 4 19 1 mm FPT HORIZONTAL Coil Model Number Connections Cased Coil Dim...

Page 8: ...d a copper tubing bender is recommended for small diameter tubing One should avoid sharp bends and contact of the refrigerant lines with metal surfaces 3 Refrigerant lines should be protected where th...

Page 9: ...ce seal the gap between the two units with sheet metal See figure 4 CAUTION CAUTION For horizontal applications the horizontal drain pan must be located under the indoor coil Failure to place the pan...

Page 10: ...ANT Seal the gap between the two units with appropriate sheet metal parts Figure 3 Installation of coil matched with a furnace two sizes smaller Figure 4 Installation of coil matched with a furnace of...

Page 11: ...oists wall studs floors or other structural components that could transmit compressor vibration Do not suspend refrigerant tubing from joists with rigid straps Do not attach line set to the wall When...

Page 12: ...failure of the aluminum tube Installation Evacuation LEAK TESTING The refrigeration line set must be pressurized and checked for leaks before evacuating and charging the unit To pressurize the line se...

Page 13: ...hat a problem exists if water should begin running from the auxiliary drain line Plug the unused drain connection with the plugs provided in the parts bag using a thin layer of Teflon paste silicone o...

Page 14: ...sulting in property damage personal injury or death For continuing high performance and to minimize possible equipment failure it is essential that annual maintenance be performed on this equipment Co...

Page 15: ...r labels or rating labels have been removed or defaced 5 Products on which payment to CM or to the owner s seller or installing contractor is in default 6 Products which have not been installed and ma...

Page 16: ...cific information on the current design and specifications Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but...

Reviews: