ClimateMaster Tranquility TAC026BM17S Installation, Operation & Maintenance Instructions Manual Download Page 12

Tranquility Aluminum Tube Cased Coil (TAC) 

R e v. :   A u g u s t   2 1 ,   2 0 1 8

12

G e o t h e r m a l   H e a t i n g   a n d   C o o l i n g

Figure 6: Air Coil Connection

Add-On Heat Pump Applications

The indoor coil should be located on the supply side of 

the furnace to avoid condensation damage to the furnace 

heat exchanger for add-on heat pump applications. A high 

temperature limit switch should be installed as shown 

in Figure 9 just upstream of the coil to de-energize the 

compressor any time the furnace is energized to avoid 

blowing hot air directly into the coil, elevating refrigerant 

pressures during operation. The heat pump will trip out on 

high pressure lockout without some method of disengaging 

the compressor during furnace operation. Alternatively, some 

thermostats with “dual fuel” mode will automatically de-

energize the compressor when second stage (backup) heat 

is required.

Air Coil

To obtain maximum performance of a newly manufactured 

air coil it should be cleaned before start-up. A 10% solution 

of dishwasher detergent and water is recommended for both 

sides of the coil. A thorough water rinse should follow.

*An LT2 (low temperature air coil protection) sensor is 

available for field installation. Order sensor kit number 

S17S0031N12.

Sensing Bulb

IMPORTANT: 

DO NOT perform any brazing with the TXV 

bulb attached to any line. After brazing operations have been 

completed, clamp the TXV bulb securely on the suction line 

at the 10 to 2 o’clock position with the strap provided in the 

parts bag. Insulate the TXV sensing bulb and suction line 

with the provided pressure sensitive insulation and secure 

with provided wire ties.

IMPORTANT:

 TXV sensing bulb should be located on a 

horizontal section of copper suction line, just outside of 

coil box. The copper sensing bulb must never be placed 

on any aluminum tube as this will result in galvanic 

corrosion and eventual failure of the aluminum tube.

Installation

Evacuation 

LEAK TESTING - The refrigeration line set must be pressurized 

and checked for leaks before evacuating and charging the 

unit. To pressurize the line set, attach refrigerant gauges to 

the service ports and add an inert gas (nitrogen or dry carbon 

dioxide) until pressure reaches 60-90 psig [413-620 kPa]. Never 

use oxygen or acetylene to pressure test. Use a good quality 

bubble solution to detect leaks on all connections made in the 

field. Check the service valve ports and stem for leaks. If a leak 

is found, repair it and repeat the above steps. For safety reasons 

do not pressurize system above 150 psig [1034 kPa]. System is 

now ready for evacuation and charging.

Condensate Drain Tubing

Consult local codes or ordinances for specific requirements.

IMPORTANT: 

When making drain fitting connections to the 

drain pan, use a thin layer of Teflon paste, silicone or Teflon 

tape and install hand tight.

IMPORTANT:

 When making drain fitting connections to drain 

pan, do not overtighten. Overtightening fittings can split pipe 

connections on the drain pan.

  Install drain lines so they do not block service access 

to front of the unit. Minimum clearance of 24 inches [61 

cm] is recommended for filter, coil or blower removal and 

service access.

•  Make sure unit is level or pitched slightly toward primary 

drain connection so that water will drain completely from 

the pan. (See Figure 7.)

•  Do not reduce drain line size less than connection size 

provided on condensate drain pan.

•  All drain lines must be pitched downward away from the 

unit a minimum of 1/8” per foot [11 mm per m] of line to 

ensure proper drainage.

•  Do not connect condensate drain line to a closed or 

open sewer pipe. Run condensate to an open drain or 

outdoors.

•  The drain line should be insulated where necessary to 

prevent sweating and damage due to condensate forming 

on the outside surface of the line.

TXV w/Internal 

Check Valve

Suction Line

Liquid Line

Bulb 

(Must be

Installed and

Insulated)

Equalizer

Line

*LT2

Low Temperature

Air Coil Safety 

(Optional) 

Summary of Contents for Tranquility TAC026BM17S

Page 1: ...tenance Instructions 97B0100N01 Rev August 21 2018 Tranquility Aluminum Tube Cased Coil TAC Table of Contents Model Nomenclature 3 General Information 4 Safety Inspection 5 Specifications 6 Dimensions...

Page 2: ...This page was intentionally left blank...

Page 3: ...ture AC T B 026 2 3 1 4 5 6 7 T TRANQUILITY HFC 410A MODEL TYPE AC CASED COIL CONFIGURATION 026 NOMINAL CAPACITY 038 049 REVISION LEVEL 064 M 8 COIL OPTIONS M MULTI POSITION CASED COIL S 11 FUTURE USE...

Page 4: ...r to file all necessary claims with the carrier Notify your equipment supplier of all damage within fifteen 15 days of shipment Storage Equipment should be stored in its original packaging in a clean...

Page 5: ...ion which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation or an unsafe practice which if not avoided could result in minor or moderate injury...

Page 6: ...0 42 17 5 44 5 0 120 0 157 0 199 0 246 TAC026BM21S 5 70 0 53 21 53 3 0 113 0 145 0 181 0 222 TAC038BM21S 8 55 0 79 0 062 0 086 0 112 0 140 0 170 0 202 0 236 TAC038BM24S 8 55 0 79 0 062 0 086 0 112 0...

Page 7: ...ZONTAL PRIMARY DRA N I SUCTION LINE LIQUID LINE SECONDARY DRAIN NOTE FLANGES ARE PROVIDED FOR FIELD INSTALLATION SECONDARY DRAIN 3 4 19 1 mm FPT HORIZONTAL Coil Model Number Connections Cased Coil Dim...

Page 8: ...d a copper tubing bender is recommended for small diameter tubing One should avoid sharp bends and contact of the refrigerant lines with metal surfaces 3 Refrigerant lines should be protected where th...

Page 9: ...ce seal the gap between the two units with sheet metal See figure 4 CAUTION CAUTION For horizontal applications the horizontal drain pan must be located under the indoor coil Failure to place the pan...

Page 10: ...ANT Seal the gap between the two units with appropriate sheet metal parts Figure 3 Installation of coil matched with a furnace two sizes smaller Figure 4 Installation of coil matched with a furnace of...

Page 11: ...oists wall studs floors or other structural components that could transmit compressor vibration Do not suspend refrigerant tubing from joists with rigid straps Do not attach line set to the wall When...

Page 12: ...failure of the aluminum tube Installation Evacuation LEAK TESTING The refrigeration line set must be pressurized and checked for leaks before evacuating and charging the unit To pressurize the line se...

Page 13: ...hat a problem exists if water should begin running from the auxiliary drain line Plug the unused drain connection with the plugs provided in the parts bag using a thin layer of Teflon paste silicone o...

Page 14: ...sulting in property damage personal injury or death For continuing high performance and to minimize possible equipment failure it is essential that annual maintenance be performed on this equipment Co...

Page 15: ...r labels or rating labels have been removed or defaced 5 Products on which payment to CM or to the owner s seller or installing contractor is in default 6 Products which have not been installed and ma...

Page 16: ...cific information on the current design and specifications Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but...

Reviews: