Electrical - Line Voltage
⚠
WARNING!
⚠
⚠
CAUTION!
⚠
WARNING!
To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION!
Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Standard TS Unit
Model
Compressor
HWG
Pump
FLA
Ext
Loop
Pump
FLA
Fan
Mo-
tor
FLA
Total
Unit
FLA
Min
Cir-
cuit
Amps
Max
Fuse/
HACR
(2)
RLA
LRA
Qty
PSC Electrical Data
018
9.0
48.0
1
0.40
4.0
1.0
14.4
16.7
25
024
13.5
58.3
1
0.50
4.0
1.6
19.6
22.9
35
030
12.8
64.0
1
0.50
4.0
1.8
19.1
22.3
35
036
16.0
77.0
1
0.50
4.0
1.8
22.3
26.3
40
042
16.7
79.0
1
0.50
4.0
2.2
23.4
27.5
40
048
21.8
117.0
1
0.50
4.0
2.7
29.0
34.4
50
060
26.4
134.0
1
0.50
4.0
3.8
34.7
41.3
60
ECM Electrical Data
018
9.0
48.0
1
0.40
4.0
3.9
17.3
19.6
25
024
13.5
58.3
1
0.50
4.0
3.9
21.9
25.2
35
030
12.8
64.0
1
0.50
4.0
3.9
21.2
24.4
35
036
16.0
77.0
1
0.50
4.0
3.9
24.4
28.4
40
042
16.7
79.0
1
0.50
4.0
3.9
25.1
29.2
45
048
21.8
117.0
1
0.50
4.0
6.9
33.2
38.6
60
060
26.4
134.0
1
0.50
4.0
6.9
37.8
44.4
70
070
30.8
178.0
1
0.50
4.0
6.9
42.2
49.9
80
Table 4: Tranquility
®
20 (TS) Series Electrical Data
Rated Voltage of 208-230/60/1
Min/Max Voltage of 197/254
HACR circuit breaker in USA only
All fuses Class RK-5
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.