ClimateMaster THW Series Installation, Operation & Maintenance Instructions Manual Download Page 10

Tranquility THW - 50 & 60Hz R410A - ClimateMaster Geothermal Heat Pumps - Rev.: 30 June, 2008B

10

GROUND-LOOP HEAT PUMP APPLICATIONS

Piping Installation

The typical closed loop ground source system is shown in 
Figure 3. All earth loop piping materials should be limited 
to only polyethylene fusion in inground sections of the 

loop. Galvanized or steel fitting should not be used at any 

time due to their tendency to corrode. All plastic to metal 

threaded fittings should be avoided due to their potential 

to leak in earth coupled applications and a flanged fitting 

substituted. P/T plugs should be used so that flow can 

be measured using the pressure drop of the unit heat 

exchanger in lieu of other flow measurement means. 

Earth loop temperatures can range between 25-110°F 
[-3.9 - 43.3°C]. Upon completion of the ground loop piping, 
pressure test the loop to assure a leak free system. 
Horizontal Systems: test individual loops as installed. Test 
entire system when all loops are assembled.
Vertical U-Bends and Pond Loop Systems: test vertical U-
bends and pond loop assemblies prior to installation with 
a hydrostatic test pressure of at least 100 psi [689 kPa].

Flushing the Earth Loop

Once piping is completed between the unit, flow center 

and the ground loop (Figure 3), final purging and charging 

of the loop is needed. A flush cart (at least a 1.5 hp [1.1 

kW] pump) is needed to achieve adequate flow velocity in 

the loop to purge air and dirt particles from the loop itself. 
An antifreeze solution is used in most areas to prevent 
freezing. All air and debris must be removed from the 
earth loop piping system before operation. Flush the loop 
with a high volume of water at a high velocity (2 fps [0.6 
m/s] in all piping) both directions. The steps below must 

be followed for proper flushing. Fill loop with water from 

a garden hose through flush cart before using flush cart 

pump to ensure an even fill. Once full, do not allow the 

water level in the flush cart tank to drop below the pump 

inlet line or air can be pumped back out to the earth loop. 

Try to maintain a fluid level in the tank above the return 

tee so that air can not be continuously mixed back into the 

fluid. 50 psi [345 kPa] surges can be used to help purge 

air pockets by simply shutting off the return valve going 

into the flush cart reservoir. This ‘dead heads’ the pump to 

50 psi [345 kPa]. To dead head the pump until maximum 
pumping pressure is reached, open the valve back up 
and a pressure surge will be sent through the loop to help 
purge air pockets from the piping system. Notice the drop 

in fluid level in the flush cart tank. 

If air is purged from 

the system, the level will drop only 1-2 [25-50mm] 

inches in a 10" [254mm] diameter PVC flush tank 

(about a half gallon) since liquids are incompressible

If the level drops more than this, flushing should continue 

since air is still being compressed in the loop fluid. Do this 

a number of times.  

When the fluid level drops less than 1-2" [25-50mm] in 

a 10" [254mm] diameter tank the flow can be reversed. 

Finally the dead head test should be checked again for 
an indication of air in the loop. 

This fluid level drop is 

your only indication of air in the loop. 

Table 3: Approximate Fluid Volume (gal.) per 

100' of Pipe

Table 4: Antifreeze Percentages by Volume

Type

Minimum Temperature for Low Temperature Protection

10°F [-12.2°C]

15°F [-9.4°C]

20°F [-6.7°C]

25°F [-3.9°C]

Methanol
100% USP food grade Propylene Glycol
Ethanol*

25%
38%
29%

21%
25%
25%

16%
22%
20%

10%
15%
14%

* Must not be denatured with any petroleum based product

Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)

Pipe

Size

Volume (gal) [liters]

Copper

1”

4.1 [15.3]

1.25”

6.4 [23.8]

2.5”

9.2 [34.3]

Rubber Hose 

1”

3.9 [14.6]

Polyethylene

3/4” IPS SDR11

2.8 [10.4]

1” iPS SDR11

4.5 [16.7]

1.25” IPS SDR11

8.0 [29.8]

1.5” IPS SDR11

10.9 [40.7]

2” IPS SDR11

18.0 [67.0]

1.25” IPS SCH40

8.3 [30.9]

1.5” IPS SCH40

10.9 [40.7]

2” IPS SCH40

17.0 [63.4]

Unit Heat Exchanger

Typical

1.0 [3.8]

Flush Cart Tank

10” Dia x 3ft tall 

[254mm x 91.4cm tall]

10 [37.9]

Summary of Contents for THW Series

Page 1: ...Data 4 Dimensional Data 5 Installation 6 Load Plumbing Installation 7 Ground Water Heat Pump Application 8 Water Quality Standards 9 Ground Loop Heat Pump Application 10 Electrical Power Wiring 13 El...

Page 2: ...or serious injury DANGER labels on unit access panels must be observed WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicate...

Page 3: ...all pipes fittings and valves before installing any of the system components Remove any dirt or trash found in or on these components Pre Installation Installation Operation and Maintenance instructio...

Page 4: ...Connection Size IPT in 1 1 1 Maximum Working Pressure Water Side Base Unit PSIG kPa 500 3445 500 3445 500 3445 DHW Option PSIG kPa 500 3445 500 3445 500 3445 Internal Source Pump w Expansion Tank PSIG...

Page 5: ...3cm Model Overall Cabinet Water Connections Electric Access Plugs 1 2 3 4 5 6 A Depth B Width C Height D Source Outdoor Water In E Source Outdoor Water Out F Load Indoor Water In G Load Indoor Water...

Page 6: ...erature and pressure combination This excludes PVC for most heating applications Insure load water flow in high temperature heating applications is at least 3 gpm per ton 3 2 l m per kW to improve per...

Page 7: ...mponents additional ball valves unions etc may be required for ease of service This drawing shows only minimum requirements Your specific installation will dictate final component selections 6 Buffer...

Page 8: ...l valve Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation Pilot operated or Taco slow closing valve s sole...

Page 9: ...pH 6 8 O2 5 ppm check for iron bacteria Iron Fouling All 0 5 ppm of Oxygen Above this level deposition will occur Corrosion Prevention pH All 6 8 5 6 8 5 Monitor treat as needed Minimize steel pipe be...

Page 10: ...sure an even fill Once full do not allow the water level in the flush cart tank to drop below the pump inlet line or air can be pumped back out to the earth loop Try to maintain a fluid level in the t...

Page 11: ...ritory manager should be consulted for the antifreeze best suited to your area Freeze protection should be maintained to 15 F 9 4 C below the lowest expected entering loop temperature For example if 3...

Page 12: ...r 240 Volt The transformers may be switched to 208V operation as illustrated on the wiring diagram By switching the Red 208V and the Orange 240V at the terminal Model Voltage Code Voltage Min Max Volt...

Page 13: ...eothermal Heat Pumps Rev 30 June 2008B 13 Figure 5 THW 50Hz Line and Low Voltage Figure 6 THW 60Hz Line and Low Voltage Electrical Line Voltage Field Low Voltage Wiring Field Line Voltage Wiring Field...

Page 14: ...Slow Closing valves on THW Series equipment Figure 9a wiring should be utilized The valve takes approximately 60 seconds to open very little water will flow before 45 seconds and it activates the com...

Page 15: ...limateMaster with a 1 4 internal flare connection as part number 39B0005N01 Electrical Low Voltage CAUTION CAUTION Refrigerant pressure activated water regulating valves should never be used with Clim...

Page 16: ...ons As the outdoor temperature decreases the heat loss of the structure increases which requires more capacity from the heating system If the water temperature is reduced as the outdoor air temperatur...

Page 17: ...F and 68 F 20 C and 20 C the water temperature in the buffer tank is adjusted accordingly For homes that are well insulated and tightly sealed the building balance point may be 55 F 13 C or lower so t...

Page 18: ...r unit forced air heating may be used for the shoulder seasons allowing quick heating to cooling changeover If this feature is used the consumer will easily be able to tell when WWSD is enabled becaus...

Page 19: ...ETS PROGRAM SETTINGS DAYLIGHT SAVINGS SET MONTH DAY YR HR MIN VACATION HOLD DATE THEN TIME SECURITY LOCKOUT TEMP ADJUST LOCKOUT TOTAL KEYPAD LOCKOUT SCREEN SETTINGS PROGRAM SCREEN SERVICE INFORMATION...

Page 20: ...ER TANK SETPOINT INPUT DEALER INFORMATION BUFFER TANK DEADBAND OUTDOOR TEMPERATURE RESET RESTORE DEFAULTS MANUAL OPERATION HOT WATER DEADBAND OUTDOOR DESIGN TEMP THW INTERFACE INSTALLER MENU MAXIMUM W...

Page 21: ...30 June 2008B 21 Electrical Wiring diagram matrix Model Diagram Number Voltage Option THW008 96B0108N01 220 50 1 THW008 96B0108N02 220 50 1 VSFP THW010 96B0108N05 230 60 1 THW010 96B0108N06 230 60 1 V...

Page 22: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 22 TYPICAL WIRING DIAGRAM THW 230 60 1 Units...

Page 23: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 23 TYPICAL WIRING DIAGRAM THW 230 60 1 Units...

Page 24: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 24 TYPICAL WIRING DIAGRAM THW 230 60 1 units with vsfp...

Page 25: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 25 TYPICAL WIRING DIAGRAM THW 230 60 1 units with vsfp...

Page 26: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 26 TYPICAL WIRING DIAGRAM THW 220 50 1 Units...

Page 27: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 27 TYPICAL WIRING DIAGRAM THW 220 50 1 Units...

Page 28: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 28 TYPICAL WIRING DIAGRAM THW 220 50 1 Units WITH VSFP...

Page 29: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 29 TYPICAL WIRING DIAGRAM THW 220 50 1 Units WITH VSFP...

Page 30: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 30 TYPICAL WIRING DIAGRAM THW 420 50 3 Units...

Page 31: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 31 TYPICAL WIRING DIAGRAM THW 420 50 3 Units...

Page 32: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 32 TYPICAL WIRING DIAGRAM THW 420 50 3 Units WITH VSFP...

Page 33: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 33 TYPICAL WIRING DIAGRAM THW 420 50 3 Units WITH VSFP...

Page 34: ...s to bring the building space up to occupancy temperatures 2 Voltage utilization range complies with ARI Standard 110 Determination of operating limits is dependent primarily upon three factors 1 ente...

Page 35: ...e for proper range and also verify heating and cooling setpoints for proper operation q System pH System water pH is 7 5 8 5 Proper pH promotes longevity of hoses and fittings q System Flushing Water...

Page 36: ...conduct the following checks a Check the voltage and current They should comply with the electrical specifications described on the unit nameplate b Look for wiring errors Check for loose terminal scr...

Page 37: ...result of the deterioration of iron or galvanized piping or components in the system or open cooling towers requiring heavy chemical treatment and mineral buildup through water use Should periodic coi...

Page 38: ...gn or improper application installation or use of CM s products or 13 Electricity or fuel costs or any increases or unrealized savings in same for any reason whatsoever CM is not responsible for 1 The...

Page 39: ...rrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any fluids refrigerant or other system components or associated labor to repair or replace the...

Page 40: ...bargain between the parties but are merely ClimateMaster s opinion or commendation of its products The management system governing the manufacture of ClimateMaster s products is ISO 9001 2000 certifi...

Reviews: