background image

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

T (ERV) Series

R e v. :   1 5   A p r i l ,   2 0 1 6

4

C l i m a t e M a s t e r   Wa t e r - S o u r c e   H e a t   P u m p s

During both the summer and winter, the ERW transfers 

moisture entirely in the vapor phase. This eliminates wet 

surfaces that retain dust and promote fungal growth as 

well as the need for a condensate pan and drain to carry 

water.

Because it is constantly rotating when in the air stream, 

the ERV is always being cleaned by air, first in one 

direction then the other. Because it is always dry, dust or 

other particles impinging on the surface during one half 

cycle, are readily removed during the next half cycle.

During the heating season, when outdoor air 

temperatures are below 10ºF, it is recommended to use 

the (optional) low ambient kit (field installed).

Low Ambient Kit is appropriate for climates with limited 

HVAC system operation when outdoor temperatures are 

below 10ºF.

The frost threshold is the outdoor temperature at which 

frost will begin to form on the ERV wheel. For Energy 

Recovery Ventilators, the frost threshold is typically below 

10ºF. Frost threshold is dependent on indoor temperature 

and humidify. The table shows how the frost threshold 

temperatures vary depending on indoor conditions.

Because Energy Recovery Ventilators have a low frost 

threshold, frost control options are not necessary in many 

climates. Where outdoor temperatures may drop below 

the frost threshold during the ERV operational hours, 

exhaust only frost control option is available.

Low Ambient Kit (Optional)

Low Ambient Kit turns off the supply blower when outdoor 

temperatures fall below the frost threshold. The exhaust 

only thermostat set points are field adjustable. Supply 

fan operation is automatically restored when the exhaust 

air temperature rises above the thermostat set point. 

Provisions for introducing make-up air into the building 

when the supply blower is off to avoid depressurization 

should be considered.

Recovery Wheel Mode

On a thermostat call for blower operation in heating, 

cooling or continuous blower, the ERW will rotate 

between fresh air and exhaust air streams. Both the 

fresh air and exhaust air blowers will also be operating to 

overcome the air resistance of the ERV.

System Check

1.   Disconnect main power.
2.   Turn to “Cont” for blower operation on thermostat 

controlled models.

3.   Restore power to unit. Observe ERV wheel rotation 

and both fresh air and exhaust air blowers are 

operating.

 

NOTE: If Low ambient kit is used the jumper 

between TB37-5 & TB37-6 should be removed. 

Also if system check out is being conducted at 

low ambient temperatures, technician should  

be aware that this kit can cause system not to 

operate.

4.   Verify that the ERV (3) three phase blower motors 

are phased sequentially ensuring correct rotation and 

operation.

  a. Disconnect power.

  b. Reverse any two field power leads to the ERV.  

c. Reapply power.

5.   Verify that both blower motors are operating under 

their full load AMP rating (FLA). The FLA can be 

found on each motor and the unit nameplate.

A.  Return Damper Settings

  Manually adjust position of field installed dampers to 

balance air flow.

 

B.  Air Flow / Blower Speed Adjustment

  Blower speed selection is accomplished by changing 

the sheave setting on both fresh air and exhaust air 

blowers. To set ERV for the required air flow (CFM), 

the external static pressure applied to the ERV (duct 

static) must be known. See the CFM vs External 

Static Pressure chart for the appropriate unit to 

determine the correct blower RPM for the specified 

CFM and External Static Pressure.

After blower speed adjustments have been made. Ensure 

that when the belt is replaced it is tensioned correctly. 

The motor mounting plate can be adjusted to tension the 

belt. If using a belt tension checker, adjust the span to the 

appropriate setting and check the belt defection force. 

The belt deflection force should be between 5-8 lbs or the 

FROST THRESHOLD TEMPERATURE

INDOOR RH AT 70ºF

FROST THRESHOLD

TEMPERATURE

20%

0ºF

30%

5ºF

40%

10ºF

Summary of Contents for TB SERIES

Page 1: ...e work In winter the ERV adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to the cold drier intake air supply during the other half rota...

Page 2: ...CL IM ATEM ASTER WATER SOURCE HEAT PUMPS T ERV Series Rev 15 April 2016 2 ClimateMaster Water Source Heat Pumps This Page Intentionally Left Blank...

Page 3: ...M for CFM and external static pressure requirements See charts in this instruction Multiple pulley arrangements are available to meet the entire range 10 Replace access panel onto the ERV unit and sec...

Page 4: ...ff to avoid depressurization should be considered Recovery Wheel Mode On a thermostat call for blower operation in heating cooling or continuous blower the ERW will rotate between fresh air and exhaus...

Page 5: ...s against the spoke flanges If hand pressure does not fully seat the segment insert the flat tip of a screw driver between the wheel rim and outer corners of the segment and apply downward force while...

Page 6: ...erate properly without balancing damper 4 See blower performance charts for airflow at various E S P 5 Filter rack with 2 pleated filters included A B C D D E I G H F H ERV Data Dimensional Data ERV S...

Page 7: ...Jack Cycle Optional J48 Jack Control Box Fresh Air J50 Jack Control Box Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harn...

Page 8: ...sh Air J50 Jack Control Box Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness J152...

Page 9: ...t 208 230V 1 PH ERV UNIT WIRING DIAGRAM Notes 1 Remove jumper to install field optional low ambient switch 2 Selective voltage terminals for proper unit voltage 3 Optional low ambient switch 4 Optiona...

Page 10: ...V UNIT WIRING DIAGRAM Notes 1 Remove jumper to install field optional low ambient switch 2 Step down transformer assembly for 460 575 volt units 3 Selective voltage terminals for proper unit voltage 4...

Page 11: ...tor Filter in Intake Hood 2HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 1200 1100 1225 1315 1405 1440 1695 1725 1400 1220 1275 1400 1480 1620 1730 1790 1600 1225 1345 1475 1615...

Page 12: ...ist Eliminator Filter in Intake Hood 3HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 2000 820 930 1015 1095 1160 1245 1315 2400 920 1010 1090 1155 1240 1305 1405 2800 1000 1085 11...

Page 13: ...MF Mist Eliminator Filter in Intake Hood 5HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 4600 820 910 990 1020 1135 1165 1225 5000 885 965 1040 1100 1160 1225 1280 5400 910 1000 1...

Page 14: ...or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair or replac...

Page 15: ...THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y T ERV Series Rev 1 5 A pri l 2 0 1 6 15 climatemaster com Notes...

Page 16: ...ment at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herein are not express warranties and do not form the basis of any b...

Reviews: