Threshold Configuration (applies to Trilogy units)
This section configures the temperature, time, and capacity thresholds associated with the heating, cooling, and hot
water (if applicable) equipment. You must configure the Equipment settings before setting the thresholds. Only the
applicable threshold settings will be displayed.
System Setting
Description
Range/Options
Default
Compressor Anticipator
Configures the sensitivity of the thermostat to the space temperature. A
lower setting will cause the unit to respond more rapidly to changes in space
temperature. A higher setting will cause the unit to respond more slowly to
changes in space temperature.
1 to 10
5
Cooling Hot Water
Cut Out
Determines the point at which the space cooling demand outpaces the ability of
the potable water heating mode to accept the heat of rejection from the cooling
mode when both are active at the same time. At this setting and above the heat
of rejection from the cooling mode will be sent to the source (ground loop).
70% to 100%
100%
Heating Hot Water
Cut Out
Potable water heating normally takes priority over space heating. This setting
determines the point at which the space heating demand will take priority over
the potable water heating demand.
70% to 100%
90%
Auxiliary Heat Dead-Band
Configures the amount of space temperature droop allowed from the heating
setpoint at maximum unit capacity before allowing auxiliary heat for space
heating.
0.0°F to 5.0°F
1.0°F
Cooling Hot Water
Cut Out Offset
This setting establishes the maximum acceptable space temperature rise
during the cooling mode while the heat from the space is being rejected into
the potable hot water. If the space temperature rises more than this amount,
the potable water heating mode will be terminated and the cooling mode will
reject the heat from the space to the source (ground loop).
0.5°F to 1.5°F
0.5°F
Heating Hot Water
Cut Out Offset
This setting establishes the maximum acceptable space temperature drop
during the potable hot water mode before the unit switches to the space
heating mode. If the space temperature drops more than this amount, the
potable water heating mode will be terminated and the space heating mode will
be activated.
0.5°F to 1.5°F
1.0°F