Threshold Configuration (applies to Trilogy units)

This section configures the temperature, time, and capacity thresholds associated with the heating, cooling, and hot 

water (if applicable) equipment. You must configure the Equipment settings before setting the thresholds. Only the 

applicable threshold settings will be displayed.

System Setting

Description

Range/Options

Default

Compressor Anticipator

Configures the sensitivity of the thermostat to the space temperature. A 

lower setting will cause the unit to respond more rapidly to changes in space 

temperature. A higher setting will cause the unit to respond more slowly to 

changes in space temperature.

1 to 10

5

Cooling Hot Water 

Cut Out

Determines the point at which the space cooling demand outpaces the ability of 

the potable water heating mode to accept the heat of rejection from the cooling 

mode when both are active at the same time. At this setting and above the heat 

of rejection from the cooling mode will be sent to the source (ground loop).

70% to 100%

100%

Heating Hot Water 

Cut Out

Potable water heating normally takes priority over space heating. This setting 

determines the point at which the space heating demand will take priority over 

the potable water heating demand.

70% to 100%

90%

Auxiliary Heat Dead-Band

Configures the amount of space temperature droop allowed from the heating 

setpoint at maximum unit capacity before allowing auxiliary heat for space 

heating.

0.0°F to 5.0°F

1.0°F

Cooling Hot Water 

Cut Out Offset

This setting establishes the maximum acceptable space temperature rise 

during the cooling mode while the heat from the space is being rejected into 

the potable hot water. If the space temperature rises more than this amount, 

the potable water heating mode will be terminated and the cooling mode will 

reject the heat from the space to the source (ground loop).

0.5°F to 1.5°F

0.5°F

Heating Hot Water 

Cut Out Offset

This setting establishes the maximum acceptable space temperature drop 

during the potable hot water mode before the unit switches to the space 

heating mode. If the space temperature drops more than this amount, the 

potable water heating mode will be terminated and the space heating mode will 

be activated.

0.5°F to 1.5°F

1.0°F

Summary of Contents for iGate AWC99U01

Page 1: ...ystem Configuration 4 Thermostat Settings 5 User Settings 5 Alert Configuration 6 System Settings 7 Equipment Settings 8 Configuration 8 Clear Fault History 11 Unit Manual Operation 12 Operating Infor...

Page 2: ...ASTER WATER SOURCE HEAT PUMPS These instructions are intended to be used by the installer or service personnel End users are NOT advised to change or modify any of these settings Doing so may cause th...

Page 3: ...lose to or in a frequently used room preferably on an inside partitioning wall On a section of wall without pipes or duct work Thermostat should NOT be mounted Close to a window on an outside wall or...

Page 4: ...re so that the insulation extends to the terminal block When the wire is installed properly to the terminal block there should be no copper exposed 22 AWG shielded wire is required when installing a r...

Page 5: ...ng the user to enter a 4 digit security PIN Disabled Enabled Disabled Security PIN requires Security to be enabled 4 digit security PIN for restricting access 0000 9999 Active Backlight Adjusts the ba...

Page 6: ...sensor can detect presence but also increases the possibility of a false presence High Medium Low Medium Wireless Configures Wi Fi functionality of the thermostat Enabled Disabled Enabled If disabled...

Page 7: ...lected amount 5 F to 5 F in 1 F increments 2 5 C to 2 5 C in 0 5 C increments 0 F 0 C Humidity Offset Allows for calibration of the humidity sensor by the selected amount 9 to 9 in 1 increments 0 Remo...

Page 8: ...onnecting the Wi Fi requires setting up the thermostat using the myUplink mobile application in order to re establish Wi Fi connectivity Disabling this function after the thermostat has been set up an...

Page 9: ...the cooling mode will be sent to the source ground loop 70 to 100 100 Heating Hot Water Cut Out Potable water heating normally takes priority over space heating This setting determines the point at wh...

Page 10: ...Airflow Configures the unit airflow during the emergency heat mode if applicable Cool Stage 1 Airflow applies to Tranquility units Configures the unit airflow while operating at minimum capacity in th...

Page 11: ...te for the water heating mode The variable speed potable water pump will adjust the potable water flow to maintain the selected temperature difference between the entering and leaving potable water du...

Page 12: ...s data set allows the service technician to view the real time status of all physical inputs switches temperature sensor readings as well as the operational status of the heat pump from the myUplink m...

Page 13: ...ve Water Coil EEV1 Position Current position of the heating electronic expansion valve in steps 0 fully closed 1040 fully open Air Coil EEV2 Status QE models only Status of the cooling electronic expa...

Page 14: ...rature reading 40 F Hum Sensor Failure Humidity sensor timed out Humidity reading is 99 Humidity reading is 0 Humidity Range High Humidity reading 90 Humidity Range Low Humidity reading 10 Outdoor Sen...

Page 15: ...climatemaster com 15 iGate Connect Programmable Thermostat Revised Dec em b er 20 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY Notes...

Page 16: ...ct ClimateMaster s Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herein are not express war...

Reviews: