36

Safety Features – CXM/DXM Controls, Cont’d.

If a UPS condition occurs, the control will immediately 

go to UPS warning. The status LED will remain on as 

if the control is in normal mode. Outputs of the control, 

excluding LED and alarm relay, will NOT be affected 

by UPS. The UPS condition cannot occur during a 

compressor off cycle. During UPS warning, the alarm 

relay will cycle on and off. The cycle rate will be “on” for 5 

seconds, “off” for 25 seconds, “on” for 5 seconds, “off” for 

25 seconds, etc.

UPS warning code = 8

Swapped LT1/LT2 thermistors:

 During test mode, the 

control monitors to see if the LT1 and LT2 thermistors are 

in the appropriate places. If the control is in test mode, the 

control will lockout with code 9 after 30 seconds if:

a.  The compressor is on in the cooling mode and the 

LT1 sensor is colder than the LT2 sensor, or:

b.  The compressor is on in the heating mode and the 

LT2 sensor is colder than the LT1 sensor.

Swapped LT1/LT2 thermistor code = 9.

ESD (DXM only):

 The ESD (Emergency Shut Down) 

mode can be enabled from an external common signal to 

terminal ESD to shut down the unit. The green status light 

will flash code 3 when the unit is in ESD mode. 

ESD mode = code 3 (green “status” LED)

CXM/DXM CONTROLS

Diagnostic Features -

 The LED on the CXM board 

advises the technician of the current status of the CXM 

control. The LED can display either the current CXM mode 

or the last fault in memory if in test mode. If there is no 

fault in memory, the LED will flash Code 1 (when in test 

mode).

The green status LED and red fault LED on the DXM 

board advise the technician of the current status of the 

DXM control. The status LED will indicate the current 

mode that the DXM control is in. The fault LED will 

ALWAYS flash a code representing the LAST fault in 

memory. If there is no fault in memory, the fault LED will 

flash Code 1. The yellow test LED will turn on when in 

test mode. 

CXM/DXM Control Start-up Operation -

 The control 

will not operate until all inputs and safety controls are 

checked for normal conditions. The compressor will have 

a 5 minute anti-short cycle delay at power-up. The first 

time after power-up that there is a call for compressor, 

the compressor will follow a 5 to 80 second random 

start delay. After the random start delay and anti-short 

cycle delay, the compressor relay will be energized. On all 

subsequent compressor calls, the random start delay is 

omitted.

Environment -

This unit is designed for indoor installation 

only. Do not install in an area subject to freezing or where 

humidity levels can cause cabinet condensation.

Power Supply -

 A voltage variation of +/- 10% of 

nameplate utilization voltage is acceptable.

Operation and performance is primarily dependent upon 

water temperatures, water flow rates and ambient air 

temperature. This water to water heat pump is capable of 

operating over a wide temperature range and with flow 

rates of between 1.5 GPM (.1 l/s) and 3 GPM (.19 l/s) per 

ton, however usually no more than one of these factors 

may be at a minimum or maximum level at a time.

The commissioning table

 indicates water temperatures 

which are suitable for initial unit commissioning in an 

environment where the flow rate and water temperature 

is not yet stable and to avoid nuisance shut down of the 

units freeze and refrigerant pressure safeties.   

The operating table

 indicates the maximum and 

minimum ranges of the unit. 

For more specific unit performance reference the product 

catalog, the submittal data sheets or contact your supplier 

for assistance.

BUILDING COMMISSIONING

Cooling

Heating

Unit Size

036

060/120 170/340

036

060/120 170/340

Source Min/Max

50/110  50/120

50/90

30/80

30/80

50/70

Load Min/Max

60/80

60/90

60/90

60/120

60/120

80/120

Ambient Min/Max

45/110

39/85

BUILDING OPERATING

Cooling

Heating

Unit Size

036

060/120 170/340

036

060/120 170/340

Source Min/Max

50/120

50/120

50/110

20/80

20/80

20/70

Load Min/Max

50/90

50/90

50/90

60/130

60/130

60/120

Ambient Min/Max

45/110

39/85

Summary of Contents for EarthPure Tranquility TMW Series

Page 1: ...11 Ground Water Heat Pump Applications 12 13 Water Quality Standards 12 Ground Loop Heat Pump Applications 14 15 Electrical Line Voltage 16 Electrical Accessories 17 Electrical Line Voltage 18 Electri...

Page 2: ...C LI MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 2 This Page Intentionally Left Blank...

Page 3: ...TEMPERATURE MODELTYPE W WATERTO WATER HEATPUMP CONFIGURATION UNIT SIZE 036 E F G H REVISION LEVEL A CURRENT VOLTAGE CONTROLS CABINET INSULATION 1 COMMERCIALEXTENDED RANGE HOT WATER GENERATOR OPTIONS T...

Page 4: ...ates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation or an unsafe practice which if not avoided could...

Page 5: ...each unit The installation site chosen should include adequate service clearance around the unit Before unit start up read all manuals and become familiar with the unit and its operation Thoroughly ch...

Page 6: ...es 400 2 758 Model TMW036 TMW060 TMW120 TMW170 TMW340 Compressor qty Scroll 1 Scroll 2 Scroll 1 Scroll 2 Factory Charge R410A lbs kg Circuit 4 5 2 04 5 5 2 49 5 5 2 49 14 9 6 75 14 9 6 75 Indoor Load...

Page 7: ...L K 1 0 2 5 cm 1 2 3 4 5 6 J H G F E D 1 3 5 Required Service Access Optional Service Access Required Service Acce Optional Service Access B C A 1 8 4 6 cm 1 3 3 3 cm 2 7 6 9 cm 1 0 2 5 cm 3 Ft 3 Ft N...

Page 8: ...KO 4 5 114 2 IPT Water Connections 15 0 381 5 4 138 21 0 533 Fault Run Lights 64 5 1638 Left Side View Front View Top View Load Source Side Refrig Circuit Access Panel Front Compressor Access Panel E...

Page 9: ...ng the flared surfaces of the joint PIPING INSTALLATION TMW Unit Location These units are not designed for outdoor installation Locate the unit in an INDOOR area that allows enough space for service p...

Page 10: ...fittings at one end to prevent kinking during installation Refer to Figure 1 for an illustration of a Supply Return Hose Kit Male adapters secure hose assemblies to the unit and risers Install hose as...

Page 11: ...ecommends 2 5 gpm per ton Air Pad or Extruded polystyrene insulation board Unit Power Disconnect Pressure Tank Flow Regulator Water Control Valve P T Plugs Water Out Shut Off Valve Boiler Drains Water...

Page 12: ...sulfate compounds All 0 5 ppm Maximum Maximum Allowable at maximum water temperature Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS...

Page 13: ...UTION Many units are installed with a factory or field supplied manual or electric shut off valve DAMAGE WILL OCCUR if shut off valve is closed during unit operation A high pressure switch must be ins...

Page 14: ...Antifreeze Percentages by Volume Antifreeze In areas where minimum entering loop temperatures drop below 40 F 5 C or where piping will be routed through areas subject to freezing anti freeze is needed...

Page 15: ...ze 208 Volt Operation All 208 230 Volt units are factory wired for 208 Volt The transformers may be switched to 230V operation as illustrated on the wiring diagram by switching the Red 208V and the Or...

Page 16: ...T1 jumper should be clipped when antifreeze is used Model Voltage Code Volatge Voltage Min Max Compressor Total Unit FLA Min Circuit Amps SCCR rms Symetrical SCCR Volts Maximum Max Fuse HACR Qty RLA L...

Page 17: ...HP Switch Circuit 1 VR3 NO RED RED 2 4 Refrigerant HP Switch Circuit 2 VR3 NO RED RED 6 8 Refrigerant HP Switch Circuit 1 VR3 NO RED RED 2 4 Refrigerant HP Switch Circuit 2 VR3 NO RED RED Coil Valve R...

Page 18: ...uit to minimize vibration and sound transmission to the building 208 Volt Operation All 208 230 Volt units are factory wired for 208 Volt The transformers may be switched to 230V operation as illustra...

Page 19: ...e temperature when using antifreezes It should be noted that the extended range option should be specified to operate the TMW Series at entering water temperatures below 60 F Figure 6a TMW036 060 Low...

Page 20: ...460 60 3 575 60 3 96B0224N02 208 230 60 1 TMW060 ONLY TMW120 96B0225N02 208 230 60 1 CXM 96B0225N03 208 230 60 3 460 60 3 575 60 3 96B0225N05 208 230 60 1 DXM 96B0225N06 208 230 60 3 460 60 3 575 60...

Page 21: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 21 Typical Wiring Diagram Three Phase TMW170 Units with CXM Controller...

Page 22: ...MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 22 Typical Wiring Diagram Three Phase TMW340 Units with CXM MPC Contro...

Page 23: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 23 Typical Wiring Diagram Three Phase TMW340 Units with CXM Controller...

Page 24: ...I MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 24 Typical Wiring Diagram Three Phase TMW340 Units with DXM Controll...

Page 25: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 25 Typical Wiring Diagram Three Phase TMW170 Units with DXM Controller...

Page 26: ...C LI MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 26 Typical Wiring Diagram Three Phase TMW170 Units with CXM CE...

Page 27: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 27 Typical Wiring Diagram Three Phase TMW170 Units with DXM CE...

Page 28: ...MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 28 Typical Wiring Diagram Three Phase TMW340 Units with CXM Controlle...

Page 29: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 29 Typical Wiring Diagram Three Phase TMW340 Units with DXM Controller CE...

Page 30: ...I MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 30 Typical Wiring Diagram Three Phase TMW120 Units with CXM Controll...

Page 31: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 31 Typical Wiring Diagram Single Phase TMW036 Units...

Page 32: ...Options Note In the following field configuration options jumper wires should be clipped ONLY when power is removed from the CXM control Water coil low temperature limit setting Jumper 3 JW3 LT1 Low...

Page 33: ...pen LT1 Fault Slow Flash Flashing Code 4 Open LT2 Fault Slow Flash Flashing Code 5 Open CO Fault Slow Flash Flashing Code 6 Open Over Under Voltages Slow Flash Flashing Code 7 Open closed after 15 min...

Page 34: ...ides selection of boilerless changeover temperature set point Note that the LT1 thermistor is sensing refrigerant temperature between the coaxial heat exchanger and the expansion device TXV or cap tub...

Page 35: ...ec pause 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure fault If...

Page 36: ...ult LED will flash Code 1 The yellow test LED will turn on when in test mode CXM DXM Control Start up Operation The control will not operate until all inputs and safety controls are checked for normal...

Page 37: ...at the lowest point in the system Adjust the make up water replacement rate to equal the rate of bleed 7 Refill the system and add trisodium phosphate in a proportion of approximately one pound per 15...

Page 38: ...corrosion q Cooling Tower Boiler Check equipment for proper setpoints and operation q Standby Pumps Verify the standby pump is properly installed and in operating condition q System Controls Verify s...

Page 39: ...epair of the equipment WARNING WARNING When the disconnect switch is closed high voltage is present in some areas of the electrical panel Exercise caution when working with energized equipment WARNING...

Page 40: ...16 60 91 113 203 207 12 18 12 18 8 17 70 95 124 204 216 16 34 12 18 9 19 80 107 128 212 217 33 35 12 18 9 20 80 1 5 50 104 111 343 348 9 14 18 25 19 28 7 14 60 121 132 355 360 9 14 18 25 7 16 70 138 1...

Page 41: ...0 108 474 488 6 11 7 11 4 16 2 3 60 95 102 215 228 6 13 7 11 6 12 7 18 80 98 106 299 313 6 13 7 11 6 18 90 99 108 329 341 6 13 7 11 6 18 100 102 110 384 401 6 13 7 11 6 17 120 106 114 475 491 6 13 7 1...

Page 42: ...erioration of iron or galvanized piping or components in the system or open cooling towers requiring heavy chemical treatment and mineral buildup through water use Should periodic coil cleaning be nec...

Page 43: ...amage or insuf cient performance as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increases...

Page 44: ...result of insuf cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated lab...

Page 45: ...mize troubleshooting and costly system failures complete the following checks and data entries before the system is put into full operation Temperatures F or C Antifreeze _____ Type of Antifreeze ____...

Page 46: ...er Out Temp 12 Load Water In Pres 13 Load Water Out Pres 13a Press Drop 13b Flow Rate GPM l s Heat of Extraction Absorption or Heat of Rejection HE or HR Flow Rate x Temp Diff x Fluid Factor s e t o N...

Page 47: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 47 Notes...

Page 48: ...ted 6 12 20 Decoder Updated 6 11 20 Unit Physical and Electrical Data Updated 06 10 20 Format All Pages Updated 07 14 17 Potable Water Statement Updatedp 04 15 16 Text Updated 10 16 15 Wiring Diagram...

Reviews: