Tubing
4.5 Line Set Installation (cont.)
4.5.2.3 Outdoor Unit Above Indoor Unit
4.0 INSTALLATION
OUTDOOR UNIT ABOVE INDOOR SECTION LINE SET
67$
For applications that are considered to have a long
line set with the outdoor unit above the indoor unit
the following is required:
• Non-bleed TXV on the indoor coil or install liquid
line solenoid valve near indoor unit with flow ar
-
row pointing toward indoor unit.
• Insulated liquid line in unconditioned space only.
Insulated suction line full length.
• Follow the proper line sizing, maximum linear
and equivalent lengths, charging requirements,
and oil level adjustments spelled out in this
manual.
INSULATE SUCTION
LINE FULL LENGTH
FOR ALL APPLICATIONS
INSULATE LIQUID LINE
IN UNCONDITIONED
SPACE FOR LONG
LINE APPLICATIONS
VERIFY
SUB-COOLING
PRIOR TO
METERING
DEVICE
NON-BLEED TXV
AI INDOOR
COIL OR INSTALL
LIQUID LINE
SOLENOID VALVE
REFERENCE TABLE 2 FOR
MAXIMUM LENGTH
AND VERTICAL SEPARATION
LIMITATIONS