OPENING WINDOWS AND DOORS
The principal of your unit is to introduce fresh air, which is washed through the filter pads to
provided cool fresh air. The air is exhausted taking with it any heat loadings on the home.
Exhaust
It is essential for successful operation of evaporative air-conditioning that there be sufficient
exhaust openings in the area to be ventilated. Open doors and windows will usually provide
this.
The minimum exhaust opening should be as per the table guide set out below. It is
recommended that ceiling vents or exhaust fans be used where there is any doubt about there
being sufficient exhaust area available. Ceiling exhaust fans or ceiling vents should have a
capacity equivalent to that of the air conditioner.
MODEL
MINIMUM
EXHAUST AREA
VSS 50
0.85 m²
VSS 60
1.19 m²
VSM 65
1.48 m²
VSL 75
2.02 m²