climachill PAC12K User Manual Download Page 18

 

18/19 

 

Before  carrying  out  this  procedure,  it  is  essential  that  the  technician  is  completely 
familiar  with  the equipment  and all  its detail. It is recommended  good  practice that  all 
refrigerants  are  recovered  safely.  Prior  to  the  task  being  carried  out,  an  oil  and 
refrigerant  sample  shall  be  taken  in  case  analysis  is  required  prior  to  re-use  of 
recovered refrigerant. It is essential that electrical power is available before the task is 
commenced. 

 

a)  Become familiar with the equipment and its  operation. 

b)  Isolate system  electrically. 

c)  Before attempting the procedure, ensure  that: 

 

mechanical handling  equipment is available, if required, for handling  refrigerant 
cylinders; 

 

all personal protective equipment is available and being used correctly; 

 

the recovery process is supervised at all times by a competent person; 

 

recovery equipment and cylinders conform to the appropriate standards. 

d)  Pump down refrigerant system, if  possible. 

e)  If a vacuum is not possible, make a manifold so that refrigerant can be removed 

from  various parts of the  system. 

f)  Make sure that cylinder is situated on the scales before recovery takes place. 

g)  Start the recovery machine and operate in accordance with instructions. 

h)  Do not overfill cylinders (no more than 80 % volume liquid charge). 

i) 

Do not exceed the maximum working pressure of the cylinder, even temporarily. 

j) 

When  the  cylinders  have  been  filled  correctly  and  the  process  completed,  make 

sure that  the cylinders  and  the  equipment  are  removed  from  site  promptly  and  all 
isolation valves on the equipment are closed  off. 

k)  Recovered refrigerant shall not be charged into another 

refrigerating system 

unless it  has been cleaned and  checked. 

 

17.  LABELLING 

 

Equipment shall be labelled stating that it has been de-commissioned and emptied of 
refrigerant. The label shall be dated and signed. For appliances containing 

flammable 

refrigerants

,  ensure  that  there  are  labels  on  the  equipment  stating  the  equipment 

contains 

flammable refrigerant

 

18.  RECOVERY 

 

When  removing  refrigerant  from  a  system,  either  for  servicing  or  decommissioning,  it  is 
recommended good practice that all refrigerants are removed safely. 
 
When  transferring  refrigerant  into  cylinders,  ensure  that  only  appropriate  refrigerant 
recovery  cylinders  are  employed.  Ensure  that  the  correct  number  of  cylinders  for 
holding the total system charge is available. All cylinders to be used are designated for 
the recovered refrigerant and labelled  for that refrigerant  (i.e. special cylinders for the 
recovery  of  refrigerant).  Cylinders  shall  be  complete  with  pressure-relief  valve  and 
associated  shut-off  valves  in  good  working  order.  Empty  recovery  cylinders  are 
evacuated and, if possible, cooled before recovery  occurs. 
   
The  recovery  equipment  shall  be  in  good  working  order  with  a  set  of  instructions 
concerning  the equipment that  is at hand  and shall be suitable for the recovery  of all 
appropriate  refrigerants  including,  when  applicable, 

flammable  refrigerants

.  In 

addition,  a  set  of  calibrated  weighing  scales  shall  be  available  and  in  good  working 
order.  Hoses  shall  be  complete  with  leak-free  disconnect  couplings  and  in  good 
condition.  Before  using  the  recovery  machine,  check  that  it  is  in  satisfactory  working 
order, has been properly maintained and that any associated electrical components are 
sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if 
in  doubt. 

 

Summary of Contents for PAC12K

Page 1: ...r Conditioner and Heater With Heat Pump Technology PAC12K 12 000btu Cool Heat Portable Air Conditioner Please read this manual carefully prior to operating the product Please keep ALL packaging for duration of Warranty Period ...

Page 2: ...ammable spray on the unit 6 Confirm drainage piping is connected properly 7 Do not start or stop the unit by inserting or pulling out the power plug 8 Do not operate with wet hands 9 Close supervision is necessary when the unit is used near children The unit in not intended for use by children 10 Do not insert anything into the air outlet Do not obstruct air inlet or outlet grills 11 Do not expose...

Page 3: ...ician for repair or maintenance of this unit 28 Unplug the unit if strange sounds smell or smoke comes from it General Information Recycling This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse ...

Page 4: ...______________________ Invoice Number _______________________________________________________ WARRANTY This product comes with a 12month warranty from date of purchase as indicated on original sales receipt Please note that it is a warranty condition that ALL of the original packaging is kept for the duration of the warranty period the main box can be folded flat for storage If you need to make a ...

Page 5: ... DIAGRAM 1 Handle 2 Air inlet L 3 Control panel 4 Wind guide bar 5 Caster 6 Remote controller 7 Air inlet R 8 Air outlet 9 Dehumidification drainage nozzle 10 Air inlet grille 11 Exhaust hose set 12 Window kit ...

Page 6: ...temperature press it at timing mode to adjust timing ON OFF time press Up and Down keys simultaneously to switch Fahrenheit and Centigrade degree temperature 5 Mode key Press the key to choose cooling fan dehumidification and heating mode 6 Timer key Press the key at standby mode to set ON time Press this key at ON mode to set OFF time 7 Temperature time display window This window displays the adj...

Page 7: ...he opening at the back of the air conditioner Venting the Exhaust Air The exhaust hose should be kept as short and straight as possible so as to not restrict airflow of the exhausted air There are 3 x options with venting the exhaust air 1 You can make a hole in the wall and pass the exhaust hose through the hole in the wall this option doesn t require a window to be slightly open 2 You can pass t...

Page 8: ...l of the window kit if necessary 2 Place the window kit between the window and the window frame as shown in the images to the right Close the window onto the window kit to form a tight seal 3 Attach the exhaust duct adapter to the window kit Tabs located on the adapter will lock into place securing the adapter to the window kit Incorrect installation It s important to keep the exhaust duct smooth ...

Page 9: ... key or choosing Fan mode by pressing the remote controller the wind indicator lamp lights up Press Speed key to choose High Mid Low speed Temperature can t be set Dehumidification mode When pressing mode key or choosing dehumidification mode by pressing the remote controller the dehumidification indicator lamp lights up Remove the dehumidification water wedge insert water manifold place the other...

Page 10: ...roduct is equipped with automatic water vaporization system The condenser is cooled with the circulating of condensing water so as to improve cooling efficiency and save energy If the internal vessel is full of water the display screen will display FL and the compressor stops working automatically After power off unscrew the water cover pull out the water wedge to drain off water and it will becom...

Page 11: ... very dirty use a neutral detergent in lukewarm water and dry in the shade Put air filter back into unit close the air inlet grille Wash the filter screen once every two weeks If it is blocked by dust efficiency of the A C will be reduced Take out the air inlet grille and pull out the filter screen at both sides according to the direction shown in the following figures Put the filter screen into t...

Page 12: ...ply on Re establish the main power supply Is the water container full indicator light on Empty the water container Is the timer set Change timer settings Cooling efficiency is not satisfactory Is the air inlet or outlet blocked Clear the blocking Is there any other heat source in the room Move the heat source Are the air filters dirty Clean the air filters Is the temperature setting suitable Chang...

Page 13: ...oor area of the room shall be mentioned in the form of a table or a single figure without reference to a formula A warning to keep any required ventilation openings clear of obstruction A notice that servicing shall be performed only as recommended by the manufacturer A warning that ducts connected to an appliance shall not contain a potential ignition source When the portable air conditioner or d...

Page 14: ...erant gas used CAUTION ON FIRE READ THE MAUAL CAREFULLY BEFORE USING THE APPLIANCE R290 refrigerant gas complies with European environmental directives This appliance contains approximately 245 g of R290 refrigerant gas Appliance shall be installed operated and stored in a room with a floor area larger than 12 m2 ...

Page 15: ...h involves exposing any pipe work shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which refrigerant can possibly be released to the surrounding space Prior to work taking place the ar...

Page 16: ...es shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation Particular attention shall be paid to the following to ensure that...

Page 17: ...rigerants refrigerants purging shall be achieved by breaking the vacuum in the system with oxygen free nitrogen and continuing to fill until the working pressure is achieved then venting to atmosphere and finally pulling down to a vacuum This process shall be repeated until no refrigerant is within the system When the final oxygen free nitrogen charge is used the system shall be vented down to atm...

Page 18: ... charged into another refrigerating system unless it has been cleaned and checked 17 LABELLING Equipment shall be labelled stating that it has been de commissioned and emptied of refrigerant The label shall be dated and signed For appliances containing flammable refrigerants ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 18 RECOVERY When removing...

Page 19: ...ompressors or compressor oils are to be removed ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant The evacuation process shall be carried out prior to returning the compressor to the suppliers Only electric heating to the compressor body shall be employed to accelerate this process When oil is drained from a ...

Reviews: