Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to 
remain illuminated for the requisite time, remedial action must be taken to repair the situation and once 
completed, the unit must pass a subsequent test. For more specific information, please refer to the 
current edition of the AS 2293.3 Standard.

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 

Fault:  

The Green LED indicator is not illuminated.

 

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Fault:  

Green LED flashes once every 5seconds - Battery is disconnected 

Check: 

Battery is connected. 

 

Fault:  

Green LED blinks off once every 5 seconds - Charging very flat battery 

Action: 

Allow 20min to recover battery then recheck 

 

Fault:  

Green LED flashes at 2Hz (Fast flash) - Faulty battery 

Action: 

Replace battery 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer 
to spacing tables for installation positions):

 

 

Refer to the Technical Label for classification information. 

 

 
 
 
 
 
 
 
 
 
 
 
  

 

 

Trade Series Boxlite LED Exit

 

Installation & Maintenance Instruction Leaflet

 

 
 

Wall Mount 

 
 
 
 
 

     Ceiling Mount

 

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9207 0000 

Fax:

 +61 8 9207 0088 

 

New Zealand 

Phone:

 +64 800 548 448 

Designed in Australia to comply with the requirements 
of AS2293.3: 2005 and AS/NZS CISPR15: 2017 
 

Models:  

 

 

EBLLED-xx-xx

 

EBLLED-WM-LI

 

Economy Lithium Boxlite LED Exit 

– Wall Mount

 

EBLLED-CM-LI

 

Economy Lithium Boxlite LED Exit 

– Ceiling Mount

 

 

 

 

 
Spare Parts:

 

1560200 

Battery, Eco Lithium, 3.2V 1.1Ah   

8002715 

PCA: Duris LED Strip CT10276 

8002971 

PCA: EBLLED-LI #CT10614-L1 6C32 M/NM CF 

 

 

 

Important:

 

It  is  illegal  for  anyone,  except  for  a  licensed  electrician  to  install  or  maintain  this  product.  Before  installation, 
ensure  that  the  electricity  supply  has  been  switched  off  and  isolated.  Installation  must  be  carried  out  in 