Clevertest and Clevertest Plus   

 
Refer to the supplementary operation guide supplied with the Product. 
 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 
flashing for a period up to 2 minutes. 

 

Zoneworks and DATA Monitored Options 

 
Ultrablades  with  part  numbers  CUBPRO-ZW

,  CUBPRO-DATA 

are  fitted  with  Zoneworks 

communications  modules  (nodes).  These  fittings  are  monitored  using  either  Powerline  Carrier 
Technology that utilises the power cable to provide data communication  or a dedicated data cable 
to/from data routers installed on a dedicated data trunk connected to a central Server (can also be 
connected  via  Ethernet/Internet/Fibre).  Zoneworks  software  on  the  server  is  used  to  monitor, 
coordinate testing and collate test data from each Ultrablade and can be commissioned by a single 
push of the test switch, or scanning of the supplied barcode. The LED Test Switch indicator provides 
a multifunction indication of the status of the Ultrablade during testing and normal operation: 

State

 

LED Operation

 

Commissioned 

LED on Solid (Green) 

Un-commissioned 

LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow) 

Emergency Light Test In Progress 

LED flashes at 3s On (Yellow) & 0.5s Off 

 
In the case of the DATA version a 2-

way “figure 8” cable and terminal block facilitates the connection 

to the DATA network via a multi-drop bus (daisy chain connection).    For further information of 
installation of a Zoneworks LW system, please refer to the Zoneworks Users Guide and 
Commissioning Guide (incl. DATA version)   
 

DALI EM Option 

 
Ultrablades  with  part  numbers  CUBPRO

-DALI 

are  fitted  with  DALI  modules  (nodes)  that  facilitate 

connection  and  integration  to  3

rd

  Party  Lighting  Control  Systems.    Before  installing  the 

CUBPRO-DALI please confirm that the Lighting Control System has the capability to monitor DALI 
Emergency  Luminaires.    The  CUBPRO-DALI  will  be  addressed  and  configured  into  the  control 
system by the Lighting Control System Commissioning Technicians and not Clevertronics.     

State

 

LED Operation

 

Commissioned/ Un-commissioned 

LED on Solid (Green) 

Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

 
A 2-

way “figure 8” cable and terminal block facilitates the connection to the DALI network.    DALI 

connections are marked as Da Da.   
 

Networking: 
 

When installing the LP Ultrablade PRO on a monitored network, (

ZONEWORKS, DATA, DALI

) simply 

insert the relevant Smart Node PCA.

 

 

 

 

 

Installation:

 

The  LP  Ultrablade  Pro  LED  Exit  (CUBPRO)  is  a  recessed  ceiling  mount  fitting.  The  CUBPRO  can  be 
attached  directly  to  any  solid  surface,  or  to  a  ceiling  tile  with  the  integrated  clamping  mechanisms.  The 
CUBPRO comes  with  an  attached  Flex  and  Plug.  Please follow  the  steps  below  to  install  the  CUBPRO 
Exit: 

 

If replacing an Ultrablade, an Ultrablade to Ultrablade Pro adapter 2740054 (sold separately) is 
required) 

 

Create a cut-out (350mm x 48mm) in the mounting surface.   

 

Route the power cord to the mains connection and connect the 240VAC supply. 

 

Insert the CUBPRO into the ceiling cavity tighten the (4) clamping screws.   

 

Alternately, fix the CUBPRO to a solid surface using (4) screws through the surface material. 

 

Install the cover plate. 

 

Apply power to the fitting and test. 

 

If the CTP capabilities are activated, please affix the CTP Status Label to a visible surface.

 

Solid surface screw points 

Pull the trim out at the centre 

Lift the decal and slide out 

Ceiling Tile 

Cover Plate 

Luminaire Dimensions: 

380mm x 220mm 

Cover Plate: 

 

385mm x 67mm 

Ceiling Cut-out: 

 

350mm x 48mm   

Minimum Depth 

 

80mm 

 

 

 

Changing EXIT Legend Inserts

:

   

 

The Ultrablade Pro Exit comes with an assortment of standard legends.   
1. 

To remove the legend, grasp the centre of the bottom trim piece and pull down slightly to expose 
the legend edge. See photo. 

2. 

Grasp the bottom edge of the legend and slide the existing legend out of the blade, while working 
the edges out along the sides. 

3. 

Slide the new legend into the blade, ensuring to fit the edges into the sides then slide the legend to 
the top of the blade. Insert one bottom corner then the other. Slide the legend down into the bottom 
trim. 

 

 

Clamping screws 

Clamping screws 

 

 

Insert corners (1&2) 
then slide up (3) 

 

Insert corners (4&5), then slide down 