Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 
 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection 
from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to 
remain illuminated for the requisite time, remedial action must be taken to repair the situation and 
once completed, the unit must pass a subsequent test. For more specific information, please refer to 
the current edition of the AS 2293.3 Standard. 
 

Ultrablade Maintenance: 

 

LED Lamp Replacement:

 

 

Use only the LED Strip recommended in the 
Spares Parts list of this instruction. 

 

Disconnect battery from LED driver pack and 
cut cable tie to remove. 

 

Disconnect the signal cable from LED strip, 
loosen screw and remove the mains driver 
pack. 

 

Remove 4 self-tapping screws and unclip the 
LED strip. 

 

Install the new LED strip following the above 
procedure in reverse.

 

 

Battery Replacement:

 

 

Use only the battery recommended in the 
Spares List on this instruction. 

 

Remove the cable ties holding the battery, 
un-plug the lead from the battery connector 
remove the old battery.   

 

Plug the new battery into the battery 
connector.   

 

Secure the battery using suitable cable ties 

 

Trouble Shooting: 

Below are a list of common problems and their 
possible causes. 

 
Fault:   

The Green LED Test Switch indicator 
is not illuminated.

 

Check:    A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:   

Lamp does not illuminate in 
emergency mode. 

 

Check:    A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   

Lamp illuminates in emergency mode, 
but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at 
least 24 hours. 

 

Battery for damage.

 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 
spacing tables for installation positions), not Included 

–TH version:

 

 

Refer to the Technical Label on the Product for classification information. 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life performance 
in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-life 
performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 
 

Warranty: 

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz

   

 

 

LP

 Ultrablade Pro LED Exit 

Installation & Maintenance Instruction Leaflet

 

Victoria (Head Office & Manufacturing) 

195 Chesterville Rd 
Moorabbin VIC 3189   

Phone:

 +61 3 9559 2700   

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

   

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

   

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

   

Phone:

 +61 8 9248 3720 

Fax:

 +61 8 9248 3725 

 

New Zealand

 

Phone: 

+64

 

800 548 448 

 
 

 
 

 

Models:

 

CUBPRO-yy-xx-zz-ss-ww-vv

 

Testing: 

 

Options:

 

 

Running Man 

zz=R 

Manual Test 

 

xx = Blank  Theatre 

yy= TH 

Running Man Left Arrow  zz=RL 

Zoneworks

 

xx = ZW 

Custom Option 

ss   

Running Man Right Arrow zz=RR 

Z/W DATA   

 

xx = DATA  Black 

vv = BLK  Double sided R/M 

zz=DS-R 

DALI Comp.         

 

xx = DALI 

Special Cable Option

 

Double sided R/M Arrow  zz=DS-RAOW 

Clevertest 

xx = CT     

ww = F5C, 5C,

 

F3C 

Vertical R/M Right Arrow  zz=VRR 

(NOTE: -CT Products supplied with the Clevertest Plus Symbol          are activated with Clevertest PLUS 
capability. Please refer to the operation guide supplied with the product for details). 
 
 
 
 

 

 

Spare Parts:   

1550130    

BATTERY: LP 3.2V 1500mAh 260mm lead no BRKT. 

2310250    

Blade Assy t/s Ultrablade Pro LED 

2740054   

Ultrablade to Ultrablade Pro adapter 

CUBPRO-CKIT   

Ultrablade Pro, Control Only, LP 

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 

ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 

accordance with the relevant Australian and International Standards. 

 

Designed in Australia to comply with the requirements 
of AS2293.3:2005 and AS/NZ CISPR:15:2017 

 

NOTE: Standard product codes with this symbol 
are enabled with Clevertest Plus capability.   