Installation:

 

The LP Gigantor LED 80 Meter Exit (CGELED) is a surface mount fitting. The CGELED can be attached 
directly to any solid surface. Please follow the steps below to install the CGELED Exit: 

 

Remove one of the end plates from the fitting. 

 

Remove the legend from the fitting. 

 

Disconnect and remove the gear tray. 

 

Locate the mounting position. Refer to the image below. 

 

Mark-out the six (6) M5 mounting holes. 

 

Mark-out the cable entry hole. 

 

Attach the fitting to the surface with appropriate fixings. 

 

Reinstall the gear tray. 

 

Connect power to the gear tray. 

 

Apply power and test the fitting. 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 
Segment Marking on the p

roduct will include an ‘’F’’ in third segment block. 

 
Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, HIVE, DALI) simply insert 
the relevant Smart Node PCA. 

 

 

Dimensions: 

 
 
 

 
 
 
 
 
 
 
 
 
 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.3 Standard. 

 
 

Maintenance: 

 
 

Battery Replacement:

 

 

Use only the battery recommended in the 
Spares List on this instruction. 
 

Trouble Shooting: 

Below are a list of common problems and their 
possible causes. 

 
Fault:  

The Green LED Test Switch 
indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in 
emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency 
mode, but only stays on for a short 
period. 

Check: 

Battery has been allowed to charge for 
at least 24 hours. 

 

Battery for damage. 

 

 

Rated Emergency Lumen Output in accordance with AS2293.1, (refer to 
spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information. 

 

Caution: 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 
 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

  

 

 

 