background image

1942362 

V1.0   

9 April 2020 

 

   

 

 

   

 

 

 

 

 

Clevertest and Clevertest Plus 

 

Refer to the supplementary operation guide supplied with the Product.

 

 

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 

flashing for a period up to 2 minutes. 

 

Zoneworks, HIVE and DATA Monitored Options

 

Fittings with part numbers -ZW

, -HV, -DATA 

are fitted with Zoneworks communications modules (nodes). 

These  fittings are monitored using either Powerline Carrier Technology that utilize  the power cable to 

provide data communication, RF transceiver modules operating in the ISM band or a dedicated data cable 

to/from data routers installed on a dedicated data trunk connected to a central Server  (can also be 

connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, coordinate 

testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a single push 

of the test switch  or by scanning the supplied barcode. The LED  Test Switch indicator provides a 

multifunction indication of the status of the fitting during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HV, DATA 

Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV 

Un-commissioned 

With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV 

Un-commissioned 

Without network connectivity 

Batt plugged-in:

 yellow 250mS, green 

250mS, yellow 250mS, green 250mS, 

green 1s 

Batt unplugged:

 red 250mS, off 

250mS, red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In Progress 

LED flashes at yellow 5s , 0ff 1s 

HV 

Emergency Light Test In Progress 

LED flashes at yellow 1s , 0ff 1s 

 

In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).    For further information of installation of 

a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 

version)   

 

DALI EM Option

 

Fittings  with part numbers  CWP2LIFE-PRO-WPPOD

-DALI 

are fitted with DALI modules (nodes) that 

facilitate connection and integration to 3

rd

  Party Lighting Control Systems.  Before installing the 

CWP2LIFE-PRO-WPPOD-DALI please confirm that the Lighting Control System has the capability to 

monitor DALI Emergency Fittings. The CWP2LIFE-PRO-WPPOD-DALI will be addressed and configured 

into the control system by the Lighting Control System Commissioning Technicians and not Clevertronics.     

State

 

LED Operation

 

Commissioned/ Un-commissioned  LED on Solid (Green) 
Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

 

A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way 

“structured wiring system” lead and plug facilitating the power and DALI connection.  DALI connections 

are marked as Da Da. 

 

CWP2LIFE-PRO-WPPOD 

Surface Mount Twin Head Emergency   

Installation & Maintenance Instruction Leaflet

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700   

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

   

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

   

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

   

Phone:

 +61 8 9248 3720 

Fax:

 +61 8 9248 3725 

 

New Zealand 

Phone:

 +64 800 548 448

 

 

 

 
 

Designed in Australia to comply with the requirements 

of AS2293.3:2005 and AS/NZS CISPR15: 2011 

NOTE: Standard product codes with this symbol              are 

enabled with Clevertest Plus capability.    Please refer to the 

operation guide supplied with the product for details.

 

Models: CWP2LIFE-PRO-WPPOD-xx 

 

Testing:

 

 

 

 

 

 

Manual Test 

 

xx = Blank   

 

 

 

Zoneworks

 

xx = ZW 

 

 

 

 

Z/W DATA   

 

xx = DATA   

 

 

 

DALI     

 

xx = DALI   

 

 

 

HIVE 

xx = HV 

 

 

 

 

Clevertest 

xx = CT       

 

 

 

 

(NOTE:  -CT Products supplied with the Clevertest Plus Symbol      are activated 

with Clevertest PLUS capability. Please refer to the operation guide supplied with the 

product for details). 

 

Spare Parts:   

1550050   

Battery, 3.2 Volt 3.2Ah Li-ion 

2750356   

LP/L10 WP POD, Gen2, 2 LED, Wht LED, Sub Assy 

AUM02370050001  CLIFE-PRO-CKIT-NP, Lifelight Pro, Control Only, 530mm, NP, CTP, OWC 
 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before 
installation, ensure that the electricity supply has been switched off and isolated. Installation must be 
carried out in accordance with the relevant Australian and International Standards. 

 

 

 

 

 

 