Mounting Bracket
Frame
LED Assembly
Light Guide
Legend
Diffuser Cover
Diffuser
Installation:
The LP Cleverfit Pro can be installed either Ceiling or Wall Mounted. The LP Cleverfit Pro uses a
“slide connect bracket base” that is mounted and wired into position first. The main body can be
installed once the base is wired or later to avoid damage during the construction phase. Please follow
the steps below to install the LP Cleverfit Pro Exit:
•
Disengage the slide connect bracket from the exit body. Position the base in the mounting position.
•
Using the bracket as a guide, mark 2 holes for mounting and one for mains access. Then install the
bracket using appropriate fixings (not supplied).
•
Configure all the mounting parts and cable entry points as below (if required) and engage the body
into the slide connect bracket. Connect mains and check that the LP Cleverfit Pro Exit is
operational
Clevertronics Self-Test (Clevertest)
Clevertronics Self-Test Cleverfit Pro (CCF
PRO
) can be programmed to perform 120 minute
discharge tests at specific intervals. A manual test is initiated by pressing the test switch 3 times
within a 5s period (immediate discharge test). A 24 hour delayed test (to allow batteries to fully
charge before a test) can be initiated by pressing the test switch and hold for 10 seconds (i.e., until
LED Test Switch indicator flashes rapidly). Refer Clevertest Operation Guide for more information.
Once the test has been completed, maintenance personnel then view the Status Indicator of each
fitting to determine a pass or failure:
SOLID GREEN
(not flashing)
NORMAL – The luminaire is in a normal state charging and awaiting
next discharge test.
SLOW YELLOW FLASH
(2s Yellow, 2s Off)
TESTING – The luminaire is currently performing a test.
VERY SLOW YELLOW & GREEN
(4s Yellow, 1s Green)
RECENTLY PASSED – The luminaire has previously tested and
passed. This indication remains for 5 days after the completion of the
test and then changes to SOLID GREEN to indicate a normal state.
FAST YELLOW & GREEN FLASH
(0.5s Yellow, 0.5s Green)
FAILED LAST TEST – The luminaire has previously tested and failed
to remain illuminated for the required duration. This indication will
remain until the required maintenance work has been completed and
the luminaire passes a subsequent discharge test.
Zoneworks Monitored Option
LP Cleverfit Pro with part numbers
CCFPRO-ZW and CCFPRO-DATA
are fitted with Zoneworks
communications modules (nodes).These fittings are monitored using Powerline Carrier Technology
that utilises the power cable to provide data communication to/from data routers installed on a
dedicated data trunk connected to a central Server. Zoneworks software on the server is used to
monitor, coordinate testing and collate test data from each fitting. Zoneworks LP Cleverfit Pro can be
commissioned by a single push of the test switch, or scanning of the supplied barcode. The LED
Test Switch indicator provides a multifunction indication of the status of the LP Cleverfit Pro during
testing and normal operation:
State
LED Operation
Commissioned
LED on Solid (Green)
Un-commissioned
LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)
Emergency Light Test in progress
LED flashes at 3s On (Yellow) & 0.5s Off
For further information of installation of a Zoneworks LW system, please refer to the Zoneworks
Users Guide ZWLW007 V1.4. & Commissioning Guide V1.6
DALI EM Option
LP Cleverfit Pro with part numbers
CCFPRO-DALI
are fitted with DALI modules (nodes) that facilitate
connection and integration to 3
rd
Party Lighting Control Systems. Before installing the
CCFPRO-DALI please confirm that the Lighting Control System has the capability to monitor DALI
Emergency Luminaires. The CCFPRO-DALI will be addressed and configured into the control
system by the Lighting Control System Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Fitting goes into emergency mode for 10 seconds
A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a
5/6way “structured wiring system” lead and plug facilitating the power and DALI connection. DALI
connections are marked as Da Da.
Networking:
When installing the LP Cleverfit Pro on a monitored network, (
ZONEWORKS, DATA, DALI
) ensure the
jumper (
J4
) is removed.
DIMENSIONS (mm)
Mounting Bracket - Top View
Ceiling Mount screw fixing points
Mounting Bracket - Front View
Cable Entry Point – Rear of bracket for wall mount,
20mm diameter, located in centre of bracket.
Wall Mount Access
Holes with Cover Plug
Wall Mount screw
fixing points
Mounting Bracket - Bottom View
Terminal Block
Terminal Block Cover
Cable Entry Point – Inside of bracket for ceiling mount,
20mm diameter, located in centre of bracket. Bracket
shown with the terminal block cover removed.
ASSEMBLY
Cable Entry Point – Top of
bracket for ceiling mount,
20mm diameter, located in
centre of bracket