background image

Mounting Bracket 

Frame 

LED Assembly 

Light Guide

 

Legend

 

Diffuser Cover 

Diffuser

 

 
 

Installation:

 

 
The LP Cleverfit Pro can be installed either Ceiling or Wall Mounted. The LP Cleverfit Pro uses a 
“slide connect bracket base” that is mounted and wired into position first. The main body can be 
installed once the base is wired or later to avoid damage during the construction phase. Please follow 
the steps below to install the LP Cleverfit Pro Exit: 
 

 

Disengage the slide connect bracket from the exit body. Position the base in the mounting position.   

 

Using the bracket as a guide, mark 2 holes for mounting and one for mains access. Then install the 
bracket using appropriate fixings (not supplied). 

 

Configure all the mounting parts and cable entry points as below (if required) and engage the body 
into the slide connect bracket. Connect mains and check that the LP Cleverfit Pro Exit is 
operational

 

 

 
 
 

Clevertronics Self-Test (Clevertest)   

 
Clevertronics  Self-Test  Cleverfit Pro  (CCF

PRO

)  can be programmed to perform 120  minute 

discharge tests at specific intervals. A manual test is initiated by pressing the test switch 3 times 
within a 5s period (immediate discharge test). A 24 hour delayed test (to allow batteries to fully 
charge before a test) can be initiated by pressing the test switch and hold for 10 seconds (i.e., until 
LED Test Switch indicator flashes rapidly). Refer Clevertest Operation Guide for more information. 
Once the test has been completed, maintenance personnel then view the Status Indicator of each 
fitting to determine a pass or failure: 

SOLID GREEN

 (not flashing) 

NORMAL – The luminaire is in a normal state charging and awaiting 
next discharge test. 

SLOW YELLOW FLASH

 

(2s Yellow, 2s Off) 

TESTING – The luminaire is currently performing a test. 

VERY SLOW YELLOW & GREEN

 

(4s Yellow, 1s Green) 

RECENTLY PASSED – The luminaire has previously tested and 
passed. This indication remains for 5 days after the completion of the 
test and then changes to SOLID GREEN to indicate a normal state. 

FAST YELLOW & GREEN FLASH

 

(0.5s Yellow, 0.5s Green) 

FAILED LAST TEST – The luminaire has previously tested and failed 
to remain illuminated for the required duration. This indication will 
remain until the required maintenance work has been completed and 
the luminaire passes a subsequent discharge test. 

 

Zoneworks Monitored Option 

 
LP  Cleverfit Pro with part numbers 

CCFPRO-ZW and  CCFPRO-DATA 

are fitted with Zoneworks 

communications modules (nodes).These fittings are monitored using Powerline Carrier Technology 
that utilises the power cable to provide data communication to/from data routers installed on a 
dedicated data trunk connected to a central Server. Zoneworks  software on the server is used to 
monitor, coordinate testing and collate test data from each fitting. Zoneworks LP Cleverfit Pro can be 
commissioned by a single push of the test switch, or scanning of the supplied barcode. The LED 
Test Switch indicator provides a multifunction indication of the status of the LP Cleverfit Pro during 
testing and normal operation: 

State

 

LED Operation

 

Commissioned 

LED on Solid (Green) 

Un-commissioned 

LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow) 

Emergency Light Test in progress 

LED flashes at 3s On (Yellow) & 0.5s Off 

 
For further information of installation of a Zoneworks LW system, please refer to the Zoneworks 
Users Guide ZWLW007 V1.4. & Commissioning Guide V1.6

 

 

DALI EM Option

 

LP Cleverfit Pro with part numbers 

CCFPRO-DALI 

are fitted with DALI modules (nodes) that facilitate 

connection and integration to 3

rd

  Party Lighting Control Systems.  Before installing the 

CCFPRO-DALI please confirm that the Lighting Control System has the capability to monitor DALI 
Emergency Luminaires.  The CCFPRO-DALI will be addressed and configured into the control 
system by the Lighting Control System Commissioning Technicians and not Clevertronics.     

State

 

LED Operation

 

Commissioned/ Un-commissioned 

LED on Solid (Green) 

Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

 
A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 
5/6way “structured wiring system” lead and plug facilitating the power and DALI connection.    DALI 
connections are marked as Da Da. 
 

Networking: 

When installing the LP Cleverfit Pro on a monitored network, (

ZONEWORKS, DATA, DALI

) ensure the 

jumper (

J4

) is removed.

 

 

 

DIMENSIONS (mm) 

Mounting Bracket - Top View 

Ceiling Mount screw fixing points

 

Mounting Bracket - Front View 

Cable Entry Point – Rear of bracket for wall mount, 
20mm diameter, located in centre of bracket. 

Wall Mount Access           
Holes with Cover Plug

 

Wall Mount screw 
fixing points

 

Mounting Bracket - Bottom View 

Terminal Block 

Terminal Block Cover 

Cable Entry Point – Inside of bracket for ceiling mount, 
20mm diameter, located in centre of bracket. Bracket 
shown with the terminal block cover removed. 

ASSEMBLY 

Cable Entry Point – Top of 
bracket for ceiling mount, 
20mm diameter, located in 
centre of bracket 

Reviews: