Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 
 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation and 
once completed, the unit must pass a subsequent test. For more specific information, please refer 
to the current edition of the AS 2293.3 Standard. 
 

Ultrablade Maintenance: 

 

LED Lamp Replacement:

 

 

Use only the LED Strip recommended in the 
Spares Parts list of this instruction. 

 

Disconnect battery from LED driver. 

 

Remove the screw holding the driver PCA. 
Remove the PCA. 

 

Remove the 4 screws holding the battery 
bracket. Remove the bracket with the 
battery. 

 

Disconnect the signal cable from LED strip. 

 

Remove 4 self-tapping screws and unclip 
the LED strip. 

 

Install the new LED strip following the 
above procedure in reverse.

 

 

Battery Replacement:

 

 

Use only the battery recommended in the 
Spares List on this instruction. 

 

Remove the battery from battery 
compartment, un-plug the lead from the 
battery connector remove the old battery.   

 

Plug the new battery into the battery 
connector.   

 

Secure the battery into the battery 
compartment 

 

Trouble Shooting: 

Below are a list of common problems and their 
possible causes. 

 
Fault:   

The Green LED Test Switch 
indicator is not illuminated.

 

Check:    A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:   

Lamp does not illuminate in 
emergency mode. 

 

Check:    A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   

Lamp illuminates in emergency 
mode, but only stays on for a short 
period. 

Check: 

Battery has been allowed to charge for 
at least 24 hours. 

 

Battery for damage.

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 
spacing tables for installation positions), not Included 

–TH version:

 

 
C0=E6.3 (8m) C90=E6.3 (8m)

 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 
 

Warranty: 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 
http://clevertronics.com.au/terms-conditions-sale-australia-nz   

 

L10

 Ultrablade Pro Surface Mount LED Exit 

 

Installation & Maintenance Instruction Leaflet

 

Victoria (Head Office & Manufacturing) 

195 Chesterville Rd 
Moorabbin VIC 3189   

Phone:

 +61 3 9559 2700   

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

   

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

   

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

   

Phone:

 +61 8 9248 3720 

Fax:

 +61 8 9248 3725 

 

New Zealand   

 

Phone: 

+64

 

800 548 448 

 
 

 
 

 

Designed in Australia to comply with the 
requirements of AS2293.3:2005 and AS/NZ CISPR:15 

 

Models: LUBPRO-SM-ww-xx-yy-zz 

Testing: 

 

 

Options:

 

 

Manual Test 

 

xx = Blank 

 

Black 

zz = BLK

 

Zoneworks

 

xx = ZW 

 

Theatre 

ww = TH 

Z/W DATA   

 

xx = DATA 

Running Man 

yy = R 

DALI Comp.         

 

xx = DALI 

 

Running Man Left Arrow 

yy = RL 

Clevertest 

xx = CT     

 

Running Man Right Arrow 

yy = RR 

 

 

 

Double Side Running Man 

yy = DS-R 

 

 

 

Double Side Running Man with Arrow 

yy = DS-RAOW 

 

 

 

Special Purpose Sign 

yy = SP 

(NOTE: -CT Products supplied with the Clevertest Plus Symbol        are activated with Clevertest PLUS 
capability. Please refer to the operation guide supplied with the product for details). 

 
Spare Parts:   

1530030 

– Battery, 3.3 Volt 2.5Ah Li-ion 

8002178 

– PCA: UBP LED strip PCB Assy   

8002940 - PCA: LUBPRO #CT10142-L8 CTP 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 

ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 

accordance with the relevant Australian and International Standards. 

NOTE: Standard product codes with this symbol       
are enabled with Clevertest Plus capability.    Please 
refer to the operation guide supplied with the product 
for details.

 

 

 

 

 