Installation:
This LWPLIFE-PRO-CM is a ceiling mount Emergency.
•
Loosen the grub screw and remove the mounting plate from the fitting.
•
Locate the installation position.
•
Using the mounting plate as a template, mark out the holes required to mount.
•
Position the plate to the surface while routing the power cable through the gland.
•
Use suitable fixings to fasten the mounting plate to the mounting surface.
•
Route and terminate the supply cables to the L, N & E terminals in the gear tray.(in the case of the
–DALI or –DATA fittings terminate the DALI or DATA cable to the terminals marked Da Da or
DATA).
•
Reinstall the main assembly and secure with the grub screws.
•
Apply power to the fitting and check operation.
•
If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four
Segment Marking on the product will include an ‘’F’’ in third segment block.
Networking:
When installing the product on a monitored network, (ZONEWORKS, DATA, HIVE, DALI) simply insert
the relevant Smart Node PCA.
Dimensions:
Testing:
When the LWPLIFE-PRO-CM unit is connected to the un-switched active, it must be allowed to charge
the battery for at least 24 hours. The emergency lamp only illuminates during a power failure. Conduct
the following tests:
•
During the first commissioning test the emergency lamp must illuminate for at least 2 hours after
disconnection from the main supply. The results of all tests are required to be recorded in a service
logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time,
remedial action must be taken to repair the situation and once completed, the unit must pass a
subsequent test.
•
To test, remove the screws holding the glass cover to the fitting to access the test button.
•
Press and hold Test Button check that the emergency lamp is On.
•
Alternately, turn off Mains Supply to the fitting. Verify the lamp is on.
•
Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Below are a list of common problems and their possible causes:
Fault: The Green LED indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected.
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1, (refer to
spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.