Installation:

 

The Jumbo LED Exit can be Wall or Ceiling Mounted:  

Wall Mounting

 (single sided) 

 

Remove one of the corner trim pieces 

 

Remove the back mounting plate. 

 

Determine power entry  

 

Position the mounting plate in the mounting position.  

 

Mark the 4 holes for mounting. Then install the appropriate fixings (not supplied). 

 

Reinstall the mounting plate to the fitting. 

 

Install the fitting on the mounting hardware, while routing the power cable through the access hole. 

 

Ensure connection of the grounding strap between the fitting and the back plate. 

 

Connect the 240VAC supply to the terminal block. 

 

Ceiling Mounting

 (single or double sided) 

 

Remove one of the corner trim panels. 

 

Remove the diffuser panel. 

 

If converting to double-sided, remove the earth strap from the back plate before removing it. 

 

Determine power entry  

 

Position the fitting in the mounting position.  

 

Mark the mounting holes at the top of the fitting. 

 

Then install using the appropriate fixings (not supplied). 

 

Position the fitting while routing the power cable and attach to the surface as required. 

 

Connect the 240VAC supply to the terminal board. 

If the CTP capabilities are activated, please affix the CTP status Label to a visible 

surface and Four 

Segment Marking on the product will include an ‘’F’’ in third segment block. 

 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, HIVE, DALI) simply insert 

the relevant Smart Node PCA. 

Dimensions: 

 

Wall Mount Plate 

 

Ceiling Mounting Plate

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 

hours. Conduct the following tests: 

 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection 

from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 

required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 

to remain illuminated for the requisite time, remedial action must be taken to repair the situation and 

once completed, the unit must pass a subsequent test. For more specific information, please refer to 

the current edition of the AS 2293.3 Standard. 

 

 

LED Exit Maintenance: 

Lamp Replacement:

 

 

Use only the LED lamp strip recommended 

on the label inside the Exit fitting or this 

instruction. 

 

To replace the lamp, loosen the cover screws 

and remove, unplug lamp connector, remove 

nuts fastening lamp strip and remove, replace 

and reassemble. 

 

Battery Replacement:

 

 

Use only the battery recommended on the 

label inside the Exit fitting and on this 

instruction. 

 

Un-plug the lead from the Inverter pack. 

Remove the old battery and install the new 

one. 

 

Reconnect the battery cable to the inverter 

pack. 

 

Trouble Shooting: 

Below are a list of common problems and their 

possible causes. 

 

Fault:   The Green LED Test Switch indicator 

is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected 

Test Switch for damage. 

 

Fault:   Lamp does not illuminate in 

emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   Lamp illuminates in emergency 

mode, but only stays on for a short 

period. 

Check:  Battery has been allowed to charge for 

at least 24 hours. 

 

Battery for damage.

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 

for –TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 

discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 

performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-

life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 

abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

 