background image

1942203 

V1.0  

19 June 2019 

 

Clevertest and Clevertest Plus 

 

Refer to the supplementary operation guide supplied with the Product.

 

 

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 
flashing for a period up to 2 minutes. 
 
 

Clevertest Essential 

Refer to the supplementary operation guide supplied with the Product.

  

 

 
Zoneworks and DATA Monitored Options

 

Cleverfits  with  part  numbers  -ZW

,  -DATA 

are  fitted  with  Zoneworks  communications  modules  (nodes). 

These fittings are monitored using either Powerline Carrier Technology that utilising the power cable to 
provide data communication or a dedicated data cable to/from data routers installed on a dedicated data 
trunk  connected  to  a  central  Server  (can  also  be  connected  via  Ethernet/Internet/Fibre).  Zoneworks 
software  on  the  server  is  used  to  monitor,  coordinate  testing  and  collate  test  data  from  each  fitting. 
Zoneworks Cleverfits can be commissioned by a single push of the test switch or scanning of the supplied 
barcode. The LED Test Switch indicator provides a multifunction indication of the status of the fitting during 
testing and normal operation: 

State

 

LED Operation

 

Commissioned 

LED on Solid (Green) 

Un-commissioned 

LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow) 

Emergency Light Test In Progress 

LED flashes at 3s On (Yellow) & 0.5s Off 

 
In the case of the DATA version a 2-

way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 
a Zoneworks LW system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. 
DATA version)  

 
DALI EM Option

 

Cleverfits  with  part  numbers 

-DALI 

are  fitted  with  DALI  modules  (nodes)  that  facilitate  connection  and 

integration  to  3

rd

  Party  Lighting  Control  Systems.    Before  installing  the  fitting  please  confirm  that  the 

Lighting  Control  System  has  the  capability  to  monitor  DALI  Emergency  Luminaires.    The  fitting  will  be 
addressed  and  configured  into  the  control  system  by  the  Lighting  Control  System  Commissioning 
Technicians and not Clevertronics.   

State

 

LED Operation

 

Commissioned/ Un-commissioned 

LED on Solid (Green) 

Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

 
A 2-

way “figure 8” cable and terminal block facilitates the connection to the DALI network.  DALI 

connections are marked as Da Da. 

 

 
 
 
 
 

 

 

L10

™ Cleverfit LED Exit

 

Installation & Maintenance Instruction Leaflet

 

 

Victoria (Head Office & Manufacturing) 

195 Chesterville Rd 
Moorabbin VIC 3189  

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9248 3720 

Fax:

 +61 8 9248 3725 

 

New Zealand 

Phone: +64 800 548 448 

Designed in Australia to comply with the requirements of 
AS2293.3: 2005 and AS/NZS CISPR15: 2011 

NOTE: Standard product codes with this symbol       are 
enabled with Clevertest Plus capability.  Please refer to the 
operation guide supplied with the product for details.

 

Models:  

 

 

LCFLED-xx-zz   

CleverFit Exit 

LCFLED-TH-xx-yy    

CleverFit Theatre Exit

 

Testing: 

 

Options:

 

 

Running Man 

yy=R 

Manual Test 

 

xx = Blank 

 

 

Running Man Left Arrow 

yy=RL 

Zoneworks

 

xx = ZW 

 

 

Running Man Right Arrow  yy=RR 

Z/W DATA  

 

xx = DATA 

 

Double sided R/M 

yy=DS-R 

DALI Comp   

 

xx = DALI 

 

 

Double sided R/M Arrow 

yy=DS-RAOW 

Clevertest Essential  xx = CTE 

 

 

Black Colour 

zz = BLK 

Clevertest 

xx = CT   

(NOTE: -CT Products supplied with the Clevertest Plus Symbol         are 
activated with Clevertest PLUS capability. Please refer to the operation 
guide supplied with the product for details). 

 

 

 

 
Spare Parts:

 

1530090 

BATTERY: L10 3.3V 2.5AH 390mm lead,noBRKT 

 

 

8002430 

PCA:Duris P5 6 LED Strip.L10,#CT10166-D1 

 

 

8002321 

PCA: LCFLED CT10164-L6 6C70 CTP DALI-COMP ZW AU 

 

 

 

 

 

 

 

 
Important:

 

It  is  illegal  for  anyone,  except  for  a  licensed  electrician  to  install  or  maintain  this  product.  Before  installation, 
ensure  that  the  electricity  supply  has  been  switched  off  and  isolated.  Installation  must  be  carried  out  in 
accordance with the relevant Australian and International Standards. 
 
 
 

 

 

 

 

 

 

Reviews: