Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 
24 hours. Conduct the following tests: 
 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit 
fails to remain illuminated for the requisite time, remedial action must be taken to repair the 
situation and once completed, the unit must pass a subsequent test. For more specific 
information, please refer to the current edition of the AS 2293.3 Standard. 
 

Ultrablade Maintenance: 

 

LED Lamp Replacement:

 

 

Use only the LED Strip recommended in 
the Spares Parts list of this instruction. 

 

Disconnect battery from LED driver. 

 

Remove the screw holding the driver PCA. 
Remove the PCA. 

 

Remove the 4 screws holding the battery 
bracket. Remove the bracket with the 
battery. 

 

Disconnect the signal cable from LED strip. 

 

Remove 4 self-tapping screws and unclip 
the LED strip. 

 

Install the new LED strip following the 
above procedure in reverse.

 

 

Battery Replacement:

 

 

Use only the battery recommended in the 
Spares List on this instruction. 

 

Remove the battery from battery 
compartment, un-plug the lead from the 
battery connector remove the old battery.   

 

Plug the new battery into the battery 
connector.   

 

Secure the battery into the battery 
compartment 

 

Trouble Shooting: 

Below are a list of common problems and their possible 
causes. 

 

Fault:   

The Green LED Test Switch indicator is 
not illuminated.

 

Check:   

A.C. is connected and is turned on. 

 

Battery is connected 
Test Switch for damage. 
 

Fault:   

Lamp does not illuminate in emergency 
mode. 

 

Check:   

A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   

Lamp illuminates in emergency mode, 
but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at 
least 24 hours. 

 

Battery for damage. 

 

Fault:   

Green LED flashes once every 5 

                    seconds-Battery is disconnected

 

Check: 

Battery is connected. 

 

Fault:   

Green LED blinks off once every 5 
seconds- Charging very flat battery

 

Allow 20min to recover battery then recheck 

 

Fault:   

Green LED flashes at 2Hz (Fast flash)- 
Faulty battery

 

Replace battery 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 
spacing tables for installation positions), not Included 

–TH version:

 

 

C0=E6.3 (8m) C90=E6.3 (8m)

 

 

Caution: 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during construction. As 
a result, any Exit & Emergency Units, on these circuits, will have their batteries discharged or “cycled”. The battery 
in this fitting has been selected to give excellent long-life performance in a controlled AS2293 testing environment. 
Excessive battery cycling will reduce through-life performance and may lead to premature battery failure. Battery 
warranty claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms. 
 

Warranty: 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 
http://clevertronics.com.au/terms-conditions-sale-australia-nz

   

 

 

Installation:

 

The  EL  Ultrablade  Pro  Surface  Mount  LED  Exit  (EUBPRO-SM-LI)  is  a  surface  mount  fitting.  The 
EUBPRO-SM  can  be  attached  directly  to  any  solid  surface.  Please  follow  the  steps  below  to  install  the 
EUBPRO Exit: 

 

Open the fitting using the 2 screws on either side of the blade. 

 

Locate the mounting surface. 

 

Drill holes in the mounting base to suit the mounting method, Ceiling or Wall (see images below). 

 

Use the mounting bracket to mark-out the mounting holes for Ceiling or Wall Mount. 

 

Drill power access hole as required. 

 

Mount the fitting using appropriate fixings. 

 

Route the power to the mains connection and connect the 240VAC supply. 

 

Attach the blade assembly to the bracket and tighten the 2 mounting screws. 

 

Apply power to the fitting and test. 

Pull the trim out at 
the centre 

Lift the decal and 
slide out 

Changing EXIT Legend Inserts

:

   

 

The Ultrablade Pro Exit comes with an assortment of standard legends.   
1. 

To remove the legend, grasp the centre of the bottom trim piece and pull down slightly to expose 
the legend edge. See photo. 

2. 

Grasp the bottom edge of the legend and slide the existing legend out of the blade, while working 
the edges out along the sides. 

3. 

Slide the new legend into the blade, ensuring to fit the edges into the sides then slide the legend to 
the top of the blade. Insert one bottom corner then the other. Slide the legend down into the bottom 
trim. 

 

 