Clevertest and Clevertest Plus 

 

Refer to the supplementary operation guide supplied with the Product.

 

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 

flashing for a period up to 2 minutes. 

The diffuser will require removal to gain access to the Test/Status Switch and LED. 

Maintained fittings (CWSQLED

M

-yy-zz) cannot be scanned with a camera using the 

Clevertest Plus 

App 

as the maintained light source interferes with the camera scanning function. To register the fitting 

manually enter the serial number from the QR code and visually read the test result and enter manually 

into 

Clevertest Plus App

 

Zoneworks, HIVE and DATA Monitored Options

 

Fittings with part numbers -ZW,  -HVG,  -DATA are fitted with Zoneworks communications modules 

(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power 

cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated 

data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also 

be connected via Ethernet/Internet/Fibre). Zoneworks software on  the server is used to monitor, 

coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a 

single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides 

a multifunction indication of the status of the fitting during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HVG, DATA  Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HVG 

Un-commissioned 

With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HVG 

Un-commissioned 

Without network connectivity 

Batt plugged-in:

 yellow 250mS, green 

250mS, yellow 250mS, green 250mS, 

green 1s 

Batt unplugged:

 red 250mS, off 250mS, 

red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In Progress 

LED flashes at yellow 5s , 0ff 1s 

HVG 

Emergency Light Test In Progress 

LED flashes at yellow 1s , 0ff 1s 

In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 

a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 

version) 

 

DALI EM Option

 

Luminaires with part numbers having -DALI are fitted with DALI modules (nodes) that facilitate connection 

and integration to 3rd Party Lighting Control Systems.  Before installing the -DALI fitting please confirm 

that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.  The -DALI 

fitting will be addressed and configured into the control system by the Lighting Control System 

Commissioning Technicians and not Clevertronics.   

State

 

LED Operation

 

Commissioned/ Un-commissioned  LED on Solid (Green) 
Emergency Light Test in progress  LED flashes at 1s On (Yellow) & 1s Off 
“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network.  DALI 

connections are marked as Da Da. 

 

 

 

CLP™ Argonaut Square LED Emergency Light

 

Installation & Maintenance Instruction Leaflet

 

 

 

NOTE: Standard product codes with this symbol 

are enabled with Clevertest Plus capability.  Please refer to 

the operation guide supplied with the product for details.

 

Australia (Head Office) 

Website: 

www.clevertronics.com.au

 

Email: 

[email protected]

 

Phone: +61 3 9559 2700  

Fax: +61 3 9559 2799

 

 

UK OFFICE 

362 Stockley Close 

West Drayton UB7 9BL 

Phone: 01895 430 255 

 

 

Models:  

 

 

CWSQLEDx-uu-yy-zz-vv

 

Testing: 

 

 

Options:

 

 

   

Manual Test 

 

zz = Blank 

 

Non-Maintained 

x = N 

   

Zoneworks

 

zz = ZW 

 

Maintained 

x = M 

   

Z/W DATA  

 

zz = DATA 

 

Microwave Sensor Hi/Lo Control  yy = MS-HL 

   

DALI REG    

 

zz = DALI 

 

Microwave Sensor Control 

yy = MS 

   

ZW Hive 

zz = HVG 

 

Low Output 

uu = LO 

   

 

 

 

Black Body 

vv = BLK 

   

 

 

Spare Parts:

 

1550290 

BATT: LP 6.4V 3.2Ah.200mm lead.Stick.Brkt 

 

 

1190320 

Sensor: M/Wave Motion, SK-503L DC 

(for -MS-HL) 

 

1330120 

LED Driver – GDY250, 26W 42VDC 610mA 

 

 

1330039 

25W DALI Driver - Programmed to 250mA - 32mA 

(for -LO) 

 

8002840 

PCA: SQ LED Array, 215mm, 400K, 3020 LED 

 

 

UKM02370050001  CCPLED-3W-CKIT, LED Power Pack, 3W, LP, OWC 

 

UKM02870130001  CCPLED-3W-CKIT-HVGEXT, LED Power Pack, 3W, HVG, LP, OWC 

 

1190325 

SENSOR:M/Wave Motion, SK-601 On/Off 

(for -MS) 

 

 

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 

ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 

accordance with the relevant British Standards. 

 

 

 

 

Reviews: