Installation:
The CLP Argonaut Square (CWSQLEDx) can be installed either Ceiling or Wall Mounted.
•
Remove the four (4) screws holding the diffuser to the base.
•
Remove the four (4) screws holding the gear tray to the base.
•
Determine the cable access point. There are 2 locations on opposite sides of the fitting for cable
gland/conduit entry. Entry can also be from the back of the base. Drill out the desired cable entry
point.
•
Drill out 4 of the mounting points in the base (see image below).
•
Using the base as a guide, mark the 4 holes for mounting and one for mains access if using back
cable entry.
•
Mount the base using appropriate fixings and seal these fixings with silicone (fill any additional entry
points with silicone also)
•
Route the power inside the base.
•
Connect the 240VAC ( ,L
SW
, L
EM
, N) supply to the terminal block of the gear tray.
•
Install the gear tray to the base.
•
Apply power to the fitting and test per the instructions.
•
If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four
Segment Marking on the product will include an ‘’F’’ in third segment block.
Dimensions:
Note:
This luminaire (with reinforced insulation between control/LED terminal and AC supply) contains non-
user replaceable light source and battery - to be replaced (if required, refer installation instructions for
battery replacement) by Clevertronics service personnel/agents or a registered electrician.
Battery Replacement:
1. Prior to any work, isolate the power to the luminaire that requires battery replacement
2. Open the fitting by removing the securing screws holding the diffuser, support diffuser doing this.
3. Remove gear tray by removing screws, support gear tray during this process.
4. Remove the Battery Connector from the Emergency Driver.
5. Remove the battery from the gear tray by removing mounting screws.
6. Replace battery, re-install screws and connect to Emergency Driver.
7. Reinstall the Gear Tray.
8. Refit the diffuser, ensure diffuser is aligned to maintain the weatherproof seal.
Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24
hours. Conduct the following tests with the Maintained Mode Off:
•
The emergency lamp must illuminate for at least 180 min after disconnection from the mains. If the
unit fails to illuminate for the requisite time, remedial action must be taken to repair the situation
and once completed, the unit must pass a subsequent test.
•
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
•
Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-
maintained operation)..
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault: The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The Li-ion battery in the luminaire has been selected to give excellent long life
performance in a controlled IEC 60598-2-22 testing environment. Excessive battery cycling will reduce
through-life performance and may lead to premature battery failure. Battery warranty claims, as a result
of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.