Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 
 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection 
from the mains supply. 

 

 

Subsequent  tests  require  the  unit  to  illuminate  for  at  least  90  minutes.  The  results  of  all  tests  are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to 
remain illuminated for  the  requisite  time,  remedial  action must  be taken  to  repair the situation  and 
once completed, the unit must pass a subsequent test. For more specific information, please refer to 
the current edition of the AS/NZS 2293.2 and AS/NZS 60598.2.22 Standards. 
 

 

Press and hold Test Button*, the product will go into Dynamic Green mode.  
 

NOTE: Initiating a Function or Duration test using the Zoneworks Software will trigger Dynamic Green for 
completion of the test.  
*The Test button needs to be held for longer than 1 seconds for the product to go into Emergency Mode.  
 

Networking: 

When  installing  the  product  on  a  monitored  network,  (ZONEWORKS,  DATA,  HIVE)  simply  insert  the 
relevant Smart Node PCA.

 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Fault:  

The Dynamic Green is not sequencing. 

Check: 

The 24 Volt/VF control is connected and turned on.   
Polarity of 24V control. 
Check that the correct interface control is selected. 
 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 
spacing tables for installation positions):

 

Please refer to the technical label on the product for classification. 

 
Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The Li-ion battery in this fitting has been selected to give excellent long life 
performance in a controlled AS/NZS 60598.2.22 testing environment. Excessive battery cycling will 
reduce through-life performance and may lead to premature battery failure. Battery warranty claims, as a 
result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.

 

 

 

LP

™ UltraBlade Pro Dynamic Green

 

Installation & Maintenance Instruction Leaflet

 

 

Victoria (Head Office & 
Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9207 0000 

Fax:

 +61 8 9207 0088 

 

New Zealand 

Phone:

 +64 800 548 448 

 
Designed in Australia to comply with the requirements of 
AS2293.3:2005(when not activated in the dynamic green or red 
cross mode) and AS/NZS CISPR22: 2009 
Note: AS2293.3 Compliance not applicable to -RU and -RD 
Products 
 
 
 

Models:     

DYGC-xUP-uu-vv-ww-xx-yy

 

Testing: 

 

 

 

Options:

 

 

Zoneworks 

xx = ZW 

 

 

Running man 

yy=R 

Z/W DATA   

xx = DATA   

 

Running man with right arrow 

yy=RR 

Zoneworks HIVE 

xx = HV 

 

 

Running man with left arrow 

yy=RL 

 

 

 

 

Running man with Up arrow 

yy=RU 

 

 

 

 

Running man with down arrow 

yy=RD 

Normally Open  

xx=NO 

 

 

Double sided DS Running Man 

yy = DS-R 

Normally Closed  

xx=NC 

 

 

Double sided Running Man Arrow yy = DS-RAOW 

Activated Only by Fire Panel  xx=AOFP   

 

Dynamic Green Disabled 

uu=DDG 

Weatherproof 

x=W 

 

 

Theater Mask 

vv=TH 

 

 

 

 

SoundEscape module 

ww=SND 

 

Spare Parts:

 

1550050 

BATT:LP 3.2V 3200mAh 70mm lead,no BRKT.

 

DYGC-UP-CKIT

 

CleverEvac UltraBlade Pro, Control Only, LP

 

DYGC-UP-HV-CKIT

 

CleverEvac UltraBlade Pro, Control Only, HV, LP

 

 

Important: 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, ensure 
that the electricity supply has been switched off and isolated. Installation must be carried out in accordance with 
the relevant Australian and International Standards. 
 
Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not 
purport to recommend its products for use in any particular application or to achieve any particular outcome. 
Purchasers and users of its products must take their own steps to ensure compliance with statutory 
requirements, safe practice and suitable application of the products 

 

Reviews: