Installation:

 

The L10 Cleverfit Pro Dynamic Red can be installed either Ceiling or Wall Mounted. The L10 Cleverfit Pro 
Dynamic Red uses a “slide connect bracket base” that is mounted and wired into position first. The main 
body  can  be  installed  once  the  base  is  wired  or  later  to  avoid  damage  during  the  construction  phase. 
Please follow the steps below to install the L10 Cleverfit Pro Dynamic Red Exit: 

 

Disengage the slide connect bracket from the exit body. Position the base in the mounting position.  

 

Using the bracket as a guide, mark 2 holes for mounting and one for mains access. Then install the 
bracket using appropriate fixings (not supplied). 

 

Remove the Terminal Block Cover. 

 

Route the AC power and 24/VF control cables through the access hole and connect to the terminal 
block as shown below. 

 

Connect positive signal of RED activation to I2 and negative signal to C (Common). 

 

Connect positive signal of GREEN activation to I1 and negative signal to C (Common). 

 

Reinstall the terminal block cover, Install the exit fitting to the slide bracket. 

 

To disable the Dynamic Green mode coming on in Emergency mode Set dipswitch 8 to OFF 
position. 

 

NOTE:

 Only to be used with the CleverEVAC Dynamic Red Bracket, do not use on similar brackets such 

as Cleverfit PRO(CCFPRO/LCFPRO). 

 

NOTE: For the Dip Switch setting to take effect the power and battery will need to be 
disconnected and reconnected. 

Dynamic Red 24 Volt (24V)/Volt Free (VF) Operation and Testing

 

Activation of the Dynamic Red/Green is controlled via 24V/VF control interface. The fitting comes pre-set 
as normally OFF. This is switched via an intelligent circuit inside the fitting. This is controlled by the 
24V/VF input from a fire panel or other source. If you would like to change the activation of the Dynamic 
Red/Green from Normally OFF to Normally ON change the Dip Switch no.6 (GREEN)/ no.7 (RED) on the 
Main LED Board (found under the Running Man diffuser) to 0. 

 

Selecting the Type of the Interface  

The fitting comes pre-set to the Volt Free(VF) control interface, to change this to 24V you will have to 
change the jumper on J1 from 1-2 (Image below) to 2-3 on the Contact board found next to battery 
compartment. Please see image below. 

 

Zoneworks and DATA Monitored Options

 

Luminaires  with  part  numbers  having  -ZW

,  -DATA 

are  fitted  with  Zoneworks  communications  modules 

(nodes).  These  fittings  are  monitored  using  either  Powerline  Carrier  Technology  that  utilises  the  power 
cable to provide data communication or a dedicated data cable to/from data routers installed on a dedicated 
data trunk connected to a central Server (can also be connected via Ethernet/Internet/Fibre). Zoneworks 
software on the server is used to monitor, coordinate testing and collate test data from each fitting and can 
be  commissioned  by  scanning  of  the  supplied  barcode.  The  LED  Test  Switch  indicator  provides  a 
multifunction indication of the status of the luminaire during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HV, DATA 

Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV 

Un-commissioned 
With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV 

Un-commissioned 
Without network connectivity 

Batt plugged-in:

 yellow 250mS, green 

250mS, yellow 250mS, green 250mS, 
green 1s 

Batt unplugged:

 red 250mS, off 

250mS, red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In Progress 

LED flashes at yellow 5s , 0ff 1s 

HV 

Emergency Light Test In Progress 

LED flashes at yellow 1s , 0ff 1s 

In the case of the DATA version a 2-

way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 
version)

 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The Li-ion battery in this fitting has been selected to give excellent long life 
performance in a controlled AS/NZS 60598.2.22 testing environment. Excessive battery cycling will 
reduce through-life performance and may lead to premature battery failure. Battery warranty claims, as a 
result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

 