background image

1944009 

V3.3 

31 March 2022 

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 
 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection 
from the mains supply. 

 

 

Subsequent  tests  require  the  unit  to  illuminate  for  at  least  90  minutes.  The  results  of  all  tests  are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to 
remain illuminated  for the  requisite  time,  remedial  action must  be  taken  to  repair the situation  and 
once completed, the unit must pass a subsequent test. For more specific information, please refer to 
the current edition of the AS/NZS 2293.2 and AS/NZS 60598.2.22 Standards. 
 

 

Press and hold Test Button, the product will go into Dynamic Red mode for the initial 60 seconds of 
the test button being pressed and then switch to Dynamic Green.  
 

NOTE: Initiating a Function or Duration test using the Zoneworks Software will trigger the Dynamic Red 
Mode for 60 seconds then Dynamic Green for further 60 Seconds.  
 

Networking: 

When  installing  the  product  on  a  monitored  network,  (ZONEWORKS,  DATA,  DALI)  simply  insert  the 
relevant Smart Node PCA.

 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Fault:  

The Dynamic Green is not sequencing. 

Check: 

The 24 Volt/VF control is connected and turned on.   
Polarity of 24V control. 
Check that the correct interface control is selected. 
 

Fault:  

The Dynamic Red is not illuminated. 

Check: 

The 24 Volt/VF control is connected and turned on.   
Polarity of 24V control. 
Check that the correct interface control is selected. 
Check that the Dynamic Red is activated on the dip switches.  

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 
spacing tables for installation positions):

 

 

 

Please refer to the technical label on the product for classification. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz

  

 

 

L10™ Cleverfit Pro Dynamic Red

 

Installation & Maintenance Instruction Leaflet

 

 

Victoria (Head Office & 
Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9207 0000 

Fax:

 +61 8 9207 0088 

 

New Zealand 

Phone:

 +64 800 548 448 

Designed in Australia to comply with the requirements of 
AS2293.3:2005(when not activated in the dynamic green or red 
cross mode) and AS/NZS CISPR22: 2009 
Note: AS2293.3 Compliance not applicable to -RU and -RD 
Products 

Models:  

 

 

DYRL-xCP-uu-vv-ww-xx-yy-zz

 

Testing: 

 

 

 

Options:

 

 

Zoneworks

 

xx = ZW 

 

 

Running man

 

yy=R

 

Z/W DATA  

 

xx = DATA   

 

Running man with right arrow

 

yy=RR

 

Zoneworks HIVE

 

xx = HV

 

 

 

Running man with left arrow

 

yy=RL

 

 

 

 

 

Running man with Up arrow

 

yy=RU

 

Normally Open 

 

xx=NO 

 

 

Running man with down arrow

 

yy=RD

 

Normally Closed 

 

xx=NC

 

 

 

Dynamic Green Disabled

 

uu=DDG

 

Activated Only by Fire 
Panel

 

xx=AOFP

   

 

Theater Mask

 

vv=TH

 

Black colour 

zz=BLK 

Weatherproof 

x=W 

 

 

SoundEscape module

 

ww=SND

 

 

Spare Parts:

 

1530230

 

BATT:L10 3.3V 5000mAh 300mm lead, noBRKT

 

 

 

8002925

 

PCA: LED Driver DYxx #CT10142

 

 

 

8002927

 

PCA: LED Driver DYxx #CT10142-L9 

(-HV only)

 

 

 

 

Important: 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, ensure 
that the electricity supply has been switched off and isolated. Installation must be carried out in accordance with 
the relevant Australian and International Standards. 
 

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not 
purport to recommend its products for use in any particular application or to achieve any particular 
outcome. Purchasers and users of its products must take their own steps to ensure compliance with 
statutory requirements, safe practice and suitable application of the products

  

Reviews: