Installation:

 

The L10 Cleverfit Pro Dynamic Green can be installed either Ceiling or Wall Mounted. The L10 Cleverfit 
Pro Dynamic Green uses a “slide connect bracket base” that is mounted and wired into position first. The 
main body can be installed once the base is wired or later to avoid damage during the construction phase. 
Please follow the steps below to install the L10 Cleverfit Pro Dynamic Green Exit: 

 

Disengage the slide connect bracket from the exit body. Position the base in the mounting position.  

 

Using the bracket as a guide, mark 2 holes for mounting and one for mains access. Then install the 
bracket using appropriate fixings (not supplied). 

 

Remove the Terminal Block Cover. 

 

Route the AC power and 24/VF control cables through the access hole and connect to the terminal 
block as shown below. 

 

Reinstall the terminal block cover, Install the exit fitting to the slide bracket. 

 

To disable the Dynamic Green mode coming on in Emergency mode Set dipswitch 8 to OFF 
position. 

 

NOTE: For the Dip Switch setting to take effect the power and battery will need to be 

disconnected and reconnected. 

Dynamic Green 24 Volt (24V)/Volt Free (VF) Operation and Testing

 

Activation of the Dynamic Green is controlled via 24V/VF control interface. The fitting comes pre-set as 
normally OFF. This is switched via an intelligent circuit inside the fitting. This is controlled by the 24V/VF 
input from a fire panel or other source. If you would like to change the activation of the Dynamic Green 
from Normally OFF to Normally ON change the Dip Switch no.6 on the Main LED Board (found under 
the Running Man diffuser) to 0. 

 

Selecting the Type of the Interface  

The fitting comes pre-set to the Volt Free(VF) control interface, to change this to 24V you will have to 
change the jumper on J1 from 1-2 (Image below) to 2-3 on the Contact board found next to battery 
compartment. Please see image below.  

 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, HIVE, DATA, DALI) simply insert 
the relevant Smart Node PCA.

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.3 Standard. 

 

Press and hold Test Button, the product will go into Dynamic Green mode.  

NOTE: Initiating a Function or Duration test using the Zoneworks Software will trigger Dynamic Green.

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage.

 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during construction. As a 
result, any Exit & Emergency Units, on these circuits, will have their batteries discharged or “cycled”. The battery in this 
fitting has been selected to give excellent long-life performance in a controlled AS2293 testing environment. Excessive 
battery cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty claims, 
as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.

 