![CLEOPATRA Cleo Premium Pro 1532 Mounting Instructions Download Page 39](http://html1.mh-extra.com/html/cleopatra/cleo-premium-pro-1532/cleo-premium-pro-1532_mounting-instructions_2622588039.webp)
39
Heating voltage supply
CAUTION!
Before connecting, ensure that the mains voltage corresponds with
the
heating voltage for the unit
(see type plate).
The connection to the heating voltage is made in accordance with the wir
ing diagram, to the
terminal block “XE1”
in the control compartment. The
customer is to install a
service switch “Q8”
(disconnecting device with a
minimum contact opening of 3 mm is an essential requirement) and a
fuse
group “F8
”
(essential requirement, fuses are to be as detailed in the fol
lowing table) in the supply line. The supply wiring is to be fed into the
unit via the clamp strap on the bottom of the unit.
Heating voltage
Max. steam
capacity
[kg/h]
Cleo
AT4 ..
Nominal power
[kW]
Nominal
current
[A]
Main fuses F8
[A]
400V3
(400 V/3~/50...60 Hz)
5
534
3.8
5.4
3x 10
8
834
6.0
8.7
3x 16
15
1534
11.3
16.2
3x 25
23
2364
17.3
24.9
3x 35
32
3264
24.0
34.6
3x 50
45
4564
33.8
48.7
3x 80
65
6564
48.8
70.4
3x 100
400V2
(400 V/2~/50...60 Hz)
5
524
3.8
9.4
3x 16
8
824
6.0
15.0
3x 25
230V3
(230 V/3~/50...60 Hz)
5
532
3.8
9.4
3x 16
8
832
6.0
15.1
3x 25
15
1532
11.3
28.2
3x 40
23
2362
17.3
43.3
3x 63
32
3262
24.0
60.2
3x 100
230V1
(230V/1~/50...60Hz)
5
522
3.8
16.3
25
8
822
6.0
26.1
40
The crosssection of the mains cable must comply with the applicable local