29
Rmin. 300 mm
Rmin. 300 mm
Ømin.
200 mm
max. 4 m
min. 300 mm
min. 20 %
–
min. 20 %
+
min. 5 %
–
min. 20 %
+
Rmin. 300 mm
min. 5 %
–
min. 20 %
+
min. 300 mm
DS35
DS22
Rmin. 300 mm
max. 4 m
– Steam distributor is mounted
less than 500 mm above the top edge
of the steam generator
:
Initially, the steam hose is led with an
upslope of at least 20 % over
a minimum height of 300 mm
above the top edge of the steam gen
erator and then down to the steam distributor with a
minimum slope
of 5 %
.
Condensate hose of the condensate drain is led down with a
minimum
slope of 20 %
, in the form of a
siphon (min. hose bend diameter Ø200
mm)
, directly into a discharge funnel.
Important!
Before putting the unit into operation, the siphon of the
condensate hose must be filled with water.
Obstacle
Install condensate drain (accessory CD..)
at the lowest point