Prometha
™
Installation
750-441
19
100 Fuel3 Actuator Out Of Pos Alm
BI
101 Fuel3 Actuator Feedback Fail Lo Alm
BI
102 Fuel3 Actuator Feedback Fail Hi Alm
BI
103 Stack Pressure Input Fail
BI
104 Hi Stack Pressure Alm
BI
105 Stack Damper Not Open Alm
BI
106 O2 Calibration Failed
BI
107 Lo Steam Pressure/Water Temp Alm
BI
108 Processor Test Fail Alm
BI
109 O2 Trim Internal Alm
BI
110 Firetube or Flextube 1 = Flextube
BI
111 Reserved for Cleaver Brooks
BI
112 VSD Limits Internal Alm
BI
113 Gas Actuator 2 Out Of Pos Alm
BI
114 Gas Actuator 2 Feedback Fail Lo Alm
BI
115 Gas Actuator 2 Feedback Fail Hi Alm
BI
116 Actuator Modbus Communication Error
BI
117 Air Actuator Modbus Comm Error Node 1
BI
118 Gas Actuator Modbus Comm Error Node 2
BI
119 Gas Act 2 Modbus Comm Error Node 3
BI
120 Oil Actuator Modbus Comm Error Node 5
BI
121 FGR Actuator Modbus Comm Error Node 7
BI
122 Reserved
BI
123 Reserved
BI
124 2nd Stg Outlet Wtr Temp Sensor Failed
BI
125 Wtr Temp Second Stg Out Hi
BI
126 Air Actuator Man Override Btn Press
BI
127 Gas Actuator 1 Man Override Btn Press
BI
128 Gas Actuator 2 Man Override Btn Press
BI
129 Oil Actuator Man Override Btn Press
BI
130 FGR Actuator Man Override Btn Press
BI
131 Fuel 3 Act 1 Man Override Btn Press
BI
132 Fuel 3 Act 2 Man Override Btn Press
BI
133 Communication from BMS Failed
BI
134 Combustion Air Pressure Hi
BI
135 Wtr FLo Lo
BI
136 Wtr Level Signal Failed
BI
137 Remote Setpoint Signal Failed
BI
138 Lo O2 Shutdown
BI
139 Air Actuator Fault
BI
140 Fuel 1 Actuator 1 Fault
BI
141 Fuel 1 Actuator 2 Fault
BI
142 Fuel 2 Actuator 1 Fault
BI
143 Fuel 2 Actuator 2 Fault
BI
144 FGR Actuator Fault
BI
145 Fuel 2 Actuator 2 Pos Deviation
BI
146 Fuel 2 Actuator 2 Feedback Lo
BI
147 Fuel 2 Actuator 2 Feedback Hi
BI
148 Fuel 2 Actuator 2 Man PB Press
BI
149 VFD Feedback Lo
BI
150 VFD Feedback Hi
BI
Hawk 1000
(continued)