1. General Information 

1.1  Introduction 

This instruction manual describes the CLAUDGEN 
Recessed Warm Air Ceiling Heaters.  

The heater is designed for discreet positioning in a 
suspended 600mm ceiling within retail or commer-
cial  premises.    It  can  fit  a  recess  as  shallow  as 
210mm. 

1.2  General

 

All  installations  must  be  in  accordance  with  the 
regulations in force in the country of use. 

These instructions must be handed to the user on 
completion of the installation. 

Installers  and  service  engineers  must  be  able  to 
demonstrate competence and be suitably qualified 
in  accordance  with  the  regulations  in  force  in  the 
country of use. 

To  ensure  continued  and  safe  operation  it  is     
recommended  that  the  appliance  is  serviced    
annually. 

The  heater  outlet  /  inlet  must  not  be  obstructed 
during use. 

 

1.3  Electrical Supply. 

 

Electrical supply is 230/240V single phase,   Neu-
tral  and  Earth.  The  maximum  cable  inlet  size  is 
4mm².  

It is recommended that the electrical supply to the 
base  unit  in  the  heater  is  via  an  appropriate 
switched 

isolator 

in 

accordance 

with 

the         

regulations in force in the country of use and must 
be via a fused isolator having a contact separation 
of greater than 3mm on all poles. 

BMS control, time switches, room thermostats and 
door  interlocks  can  be  installed  at  the  discretion 
and responsibility of the installer. 

 

All  units  must  be  wired  in  accordance  with  I.E.E 
regulations  for  the  Electrical  Equipment  of     
Buildings  and  the  installer  should  ensure  that  a 
suitable isolating switch is connected in the mains 
supply. 

1.4 Controller `W` models 

The  HE7230RF,  HE7245RF,  HE7260RF  heaters 
are supplied  without a controller. The `W` models 
will  not  work  without  the  controller.  There  are 
three  wireless  controllers  to  choose  from  in  our 
range. See section 5.1 for more details.

 

1.5 Controller standard models 

The  HE7230,  HE7245,  HE7260  heaters  are  sup-
plied  with  a  remote  controller.  The  remote  control 
unit  houses  3  double  pole  20A  rocker  switches. 
The  heater  can  also  be  controlled  remotely  via 
BMS or any controls with contact rated at 20A for 
HE7230,  HE7245  and  30A  for  HE7260.  The  con-
troller  is  wired  to  the  base  unit  via  an  appropriate 
sized cable specified by the current IEE standard. 

 

 

 

 

 

 

1.6  Location. 

All  units  should  be  installed  horizontally.  It  is  rec-
ommended  that  the  ceiling    heater  is  installed 
within the ceiling void or roof space. 
 
Care  must  be  taken  to  allow  complete  free  air 
movement into the inlet grilles of the unit to ensure 
the correct working operation of the heater. If the-
HE7230 or HE7245 heaters are mounted close to 
the  wall  or  corner  the  discharge  opening  should 
be facing the wall. The minimum distance from the 
wall or corner is 0.8m or 1.2m for the HE7260.  

 

1.7  Clearance distances 

 

It  is  recommended  that  a  minimum  clearance  of 
50mm  is  allowed  around  the  case  and  30mm 
above  the  heater.  The  clearance  allows  for  cable 
entry  and  prevents  combustible  surfaces  over-
heating.  
 
The  minimum  mounting  height  (floor  to  grille)  is 
2.2m  for  the  HE7230,  HE7245  and  2.5m  for  the 
HE7260.  The  recommended  mounting  height  is 
2.5m  for  the  HE7230,  HE7245  and  3m  for  the 
HE7260. 

CLAUDGEN Wireless controllers 

41001224 Iss 02 

Summary of Contents for HE7245

Page 1: ...2 RECESSED WARM CEILING HEATERS CATALOGUE NUMBERS HE7230 HE7245 HE7260 HE7230RF HE7245RF HE7260RF INSTALLATION AND OPERATING MANUAL Consort Equipment Products Limited Thornton Industrial Estate Milfor...

Page 2: ...at a suitable isolating switch is connected in the mains supply 1 4 Controller W models The HE7230RF HE7245RF HE7260RF heaters are supplied without a controller The W models will not work without the...

Page 3: ...tion Sole liability rests with the installer to ensure that protective safety wear such as hand eye ear and head protection is used during installation of the product 1 General Information Do not rest...

Page 4: ...free from vi bration The discharge grille and diffuser assem bly can now be fitted into the ceiling frame 4 1 Electrical Connections These units are suitable for connection to a 230 240 Volt 50 Hz si...

Page 5: ...witch supplied eg BMS then the heat output can be selected by connecting the appropriate terminals WIRED TERMINALS HE7230 HE7245 HE7260 H1 H2 F 3000W 4500W 6000W H1 F 1000W 1500W 2000W H2 F 2000W 3000...

Page 6: ...stat should be wired between the isolator switch and the heater remote switch For HE7245 HE7260 or to control more than one HE7230 heaters by a thermostat a contactor or a relay in conjunction with th...

Page 7: ...hermal cut out The units are protected from overheating in the event of fan failure or an obstruction of the free airflow by thermal cut outs If this happens the thermal cut outs switch off the applia...

Page 8: ...8...

Reviews: