2
1. General Information
1.1 Introduction
This instruction manual describes the CLAUDGEN
Recessed Warm Air Ceiling Heaters.
The heater is designed for discreet positioning in a
suspended 600mm ceiling within retail or commer-
cial premises. It can fit a recess as shallow as
210mm.
1.2 General
All installations must be in accordance with the
regulations in force in the country of use.
These instructions must be handed to the user on
completion of the installation.
Installers and service engineers must be able to
demonstrate competence and be suitably qualified
in accordance with the regulations in force in the
country of use.
To ensure continued and safe operation it is
recommended that the appliance is serviced
annually.
The heater outlet / inlet must not be obstructed
during use.
1.3 Electrical Supply.
Electrical supply is 230/240V single phase, Neu-
tral and Earth. The maximum cable inlet size is
4mm².
It is recommended that the electrical supply to the
base unit in the heater is via an appropriate
switched
isolator
in
accordance
with
the
regulations in force in the country of use and must
be via a fused isolator having a contact separation
of greater than 3mm on all poles.
BMS control, time switches, room thermostats and
door interlocks can be installed at the discretion
and responsibility of the installer.
All units must be wired in accordance with I.E.E
regulations for the Electrical Equipment of
Buildings and the installer should ensure that a
suitable isolating switch is connected in the mains
supply.
1.4 Controller `W` models
The HE7230RF, HE7245RF, HE7260RF heaters
are supplied without a controller. The `W` models
will not work without the controller. There are
three wireless controllers to choose from in our
range. See section 5.1 for more details.
1.5 Controller standard models
The HE7230, HE7245, HE7260 heaters are sup-
plied with a remote controller. The remote control
unit houses 3 double pole 20A rocker switches.
The heater can also be controlled remotely via
BMS or any controls with contact rated at 20A for
HE7230, HE7245 and 30A for HE7260. The con-
troller is wired to the base unit via an appropriate
sized cable specified by the current IEE standard.
1.6 Location.
All units should be installed horizontally. It is rec-
ommended that the ceiling heater is installed
within the ceiling void or roof space.
Care must be taken to allow complete free air
movement into the inlet grilles of the unit to ensure
the correct working operation of the heater. If the-
HE7230 or HE7245 heaters are mounted close to
the wall or corner the discharge opening should
be facing the wall. The minimum distance from the
wall or corner is 0.8m or 1.2m for the HE7260.
1.7 Clearance distances
It is recommended that a minimum clearance of
50mm is allowed around the case and 30mm
above the heater. The clearance allows for cable
entry and prevents combustible surfaces over-
heating.
The minimum mounting height (floor to grille) is
2.2m for the HE7230, HE7245 and 2.5m for the
HE7260. The recommended mounting height is
2.5m for the HE7230, HE7245 and 3m for the
HE7260.
CLAUDGEN Wireless controllers
41001224 Iss 02