10
LPCB Instrument Panel
Figure #9A
1
– Emergency Operating Instructions
2
– Manual Crank Controls
IMPORTANT: Main pump controller selector
should be in the
OFF
position when starting from
engine gauge panel. Be sure to return selector on
main pump controller and engine gauge panel to
AUTOMATIC
after completing manual run.
2.6.3 To Stop Engine
If engine is started from main pump controller use
main pump controller to stop the engine.
Engines not equipped with an engine gauge panel,
and LPCB engine, have a manual shutdown lever on
the engine for shutdown.