CKD EVD Series Manual Download Page 6

Pilot 
exhaust air

Main exhaust air

Wall

5 mm and over

Intro 4

Design & Selection

Confirm that primary pressure does not drop to less
than "set secondary pr maximum control
pressure x 0.2."

Regulator life is shortened if primary pressure is not sup-

plied for a long time while power is on. Avoid such use.

When releasing secondary control pressure, such
as air exhaust, into the atmosphere, pressure may
fluctuate depending on piping and other conditions.
Test under actual working conditions, or consult with
CKD before doing this.

Select a dryer, air filter, oil mist filter, or regulator with
a flow higher than that of this regulator.

CAUTION

Work environment
Avoid using this regulator where it will be subject to direct
sunlight, water or oil, etc. Consult with CKD when using
outside designated specifications or for special applications.

Dripproof environment
The regulator's protective structure is equivalent to
IP40. Do not install it where water, salt, dust, or cut-
ting chips are present or under pressurized or de-
pressurized conditions. Use at sites of drastic tem-
perature changes or high humidity may cause dam-
age due to dew condensation in the regulator.

Even when set to 0 MPa, secondary pressure re-
mains within 5 kPa or less. If 0 MPa is required, bleed
the secondary side or install a 3-way valve on the
secondary side to change to atmosphere, etc.

DANGER

Set power voltage and output to the specified voltage.
Using a voltage exceeding that specified could result in
malfunction, controller damage, electric shock, or fire.
Do not use a load exceeding the output rating. Failure
to observe this may result in output damage or fire.

Installation & Adjustment

Installation

WARNING

Connector pin and cables conductors color must be
checked when wiring. Check wire color with handling
precaution, since improper wire connection leads to
destruction/failure and malfunction.

Insulation of wiring must be checked.
Contact to another circuit, ground fault or terminal
insulation defective must be eliminated. Overcurrent
may be admitted to damage.

Use DC safety power supply in rated, insulated from
alternating current power, for this product. If power sup-
ply is not insulated, electric shock may result. If power
supply is not stabilized, peak magnitude exceeds rated,
and damages this product, worsening accuracy.

Stop controllers and machinery and turn power off
before wiring. Starting operation immediately after
wiring could result in unpredictable operation and
hazard. Conduct energized tests with controllers and
machinery stopped. Before starting work, remove
static electricity in personnel, tools, and devices. Use

Wiring

Secure sufficient peripheral space for operating, in-
stalling, removing, wiring, and piping the product.

Install the air filter just before the circuit using the
pneumatic component.

Install the regulator so that the exhaust port is not
blocked, and secure a space required for exhaust.

Installation

CAUTION

flexible wires, such as robot wires, for connection at
movable sections.

Do not use power voltage exceeding specifications.
The regulator could rupture or catch fire if voltage
exceeding the working range is applied or if 100 VAC
power is applied.

Short-circuiting the load could result in rupture or fire.

Individual Precautions

EVD

 Series

Summary of Contents for EVD Series

Page 1: ...1 Digitalelectropneumaticregulator EVD series CC 764A Compact high function digital control New product...

Page 2: ...ge methods Direct memory function External input signals are not required Secondary pressure is adjusted as desired with operation keys Switch output function Switch outputs built in overcurrent prote...

Page 3: ...trol Air turbine speed control Fixing of lead frames etc Assembly of chips EVD Cylinder Solenoid valve Grindstone Motor Controller EVD Air turbine EVD Tip EVD Lead frame EVD EVD Tank Magnetic tape Air...

Page 4: ...uipment or applications coming into contact with beverage or food amusement equipment emergency shutoff circuits press machine brake circuits or for safeguard Use for applications where life or assets...

Page 5: ...d valve relay etc and remove noise where generated Keep wiring to the device separate from strong magnetic fields Connect wiring to the device with a shield wire Ground the shield wire on the power su...

Page 6: ...e Do not use a load exceeding the output rating Failure to observe this may result in output damage or fire Installation Adjustment Installation WARNING Connector pin and cables conductors color must...

Page 7: ...agent on pipe connections with a brush and check for air leaks Lock the D sub connector so that it does not move Fix the fixed bed with a tool etc when releasing the screw lock CAUTION Piping The opt...

Page 8: ...m that it is operating correctly This case is made of resin Do not use solvent alco hol or detergent when cleaning because resin could be damaged Wipe off dirt with a rag dampened in a diluted neutral...

Page 9: ...kPa 0 5 F S or less 0 3 F S or less 0 2 F S or less 0 3 F S or less 0 15 F S or less 0 07 F S or less 400 min 0 2sec or less loadless 98 m s2 or less 5 to 50 5 to 50 Rc1 4 Free 250g Power supply rever...

Page 10: ...nitrile rubber Aluminum alloy SUJ Special nitrile rubber and stainless steel Silicon rubber Brass and electroless nickeling Fluoro rubber Blank C1 C3 P1 P3 None Analog 9 conductor cable 1 m Analog 9 c...

Page 11: ...age 9 for cable option dimensions 1 6 3 5 3 5 44 36 30 56 64 4 4 4 4 27 36 27 1 6 44 22 8 3 5 4 full R 7 2 32 22 42 42 4 full R 5 17 5 4 4 30 5 51 36 27 10 48 6 OUT IN 42 100 21 107 18 27 36 5 3 EXH p...

Page 12: ...ure Input signal kPa 0 0 200 400 600 100 200 300 400 600 500 Control pressure Flow rate min Working pressure 0 7MPa Working pressure 0 7MPa kPa 0 0 100 200 300 400 100 200 300 400 600 500 Control pres...

Page 13: ...ting minimum width 1kPa 0 5 F S or less 0 3 F S or less 0 2 F S or less 0 3 F S or less 0 15 F S or less 0 07 F S or less 1500 min 0 2sec or less loadless 98m s2 or less 5 to 50 5 to 50 Rc1 4 Rc3 8 Fr...

Page 14: ...ess steel Special brass and nitrile rubber Special brass and nitrile rubber Brass Nitrile rubber Steel sheet 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Blank C1 C3 P1 P3 None Analog 9 coductor cable 1...

Page 15: ...tion dimensions Rc3 8 EXH port 6 6 30 50 24 38 32 24 38 87 71 53 2 12 1 6 8 4 5 32 36 5 61 5 24 38 24 38 7 26 36 50 7 22 2 3 8 4 5 50 4 full R 52 4 133 OUT 24 38 50 IN 25 7 140 78 25 8 2 M4 depth12 D...

Page 16: ...200 300 400 600 500 Control pressure kPa 0 0 1000 2000 3000 4000 100 200 300 400 600 500 Control pressure kPa 0 0 1000 2000 3000 4000 100 200 300 400 600 500 Control pressure kPa Flow rate min Flow ra...

Page 17: ...n 0 to 10 VDC Vacant Vacant Monitor output Output short circuit protection circuit 1 to 5 VDC Switch output NPN or PNP output Error output NPN or PNP output Power supply 0V Type of input Isolator colo...

Page 18: ...M E M O M E M O 10...

Page 19: ...15 power supply max 50mA Signal generator Load Load Output short circuit protection circuit Main circuit Signal generator Pin 5 power supply Pin 13 monitor output Pin 11 analog input Pin 14 error out...

Page 20: ...8 Pin 8 bit 7 Pin 7 bit 6 Pin 6 bit 5 Pin 4 bit 4 Pin 3 bit 3 Pin 2 bit 2 Pin 1 LSB bit 1 Pin 13 switch output Pin 14 error output Pin 15 power supply max 50mA max 50mA Load Load Main circuit Pin 5 p...

Page 21: ...and setting are confirmed When Mode 1 valid is selected F4 0 tolerable range setting L tolerable range setting H is alternately displayed When Mode 2 valid is selected F4 1 lower limit setting value...

Page 22: ...pan adjustment and the setting are confirmed Note This is invalid if preset or direct memory input is selected for F1 mode F4 switch output function Screen F4 display details Switch output validity an...

Page 23: ...n F1 After setting exits setting mode and returns to screen F1 After setting exits setting mode and returns to screen F1 To select analog input Default Changing parallel input signal selection Input t...

Page 24: ...After setting exits setting mode and returns to screen F2 To use with adjusted zero span 2 seconds and over Input the set value key Moves digit key Counts up value Input the set value key Moves digit...

Page 25: ...scriptions Setting specifications Set the target pressure Range 000 to 500 Minimum setting 1 kPa Range 000 to 500 Minimum setting 1 kPa Range 00 to 50 Minimum setting 1 Range 00 to 50 Minimum setting...

Page 26: ...e and turn power on again Check the regulator s input signal set the input signal within the rated range and turn power on again Check primary pressure supply pressure within the rating and turn power...

Page 27: ...0 3 5541 1468 FAX 60 0 3 5541 1533 JOHOR BAHRU OFFICE 116 118 Jalan Rosmerah 2 17 Taman Johor Jaya 81100 Johor Bahru Malaysia PHONE 60 0 7 352 9129 FAX 60 0 7 352 9144 MELAKA OFFICE No B 10 Ground Fl...

Reviews: