Using SWA cables with Safevolt
®
50
⚠
For the reasons given above, if using SWA cable between the Safevolt
®
50 unit and the charge point or
the supply DB and the Safevolt it is important to verify that the SWA amour termination will not result in a
connection between the building CPC and the charge point CPC including the metal case of the Safevolt
unit. For instance, an SWA cable terminated in the charge point case and a building DB with a metallic
case will cause such a connection and is not allowed.
Chargepoint
E
Metal
Distribution
Board
Safevolt 50
SWA
CABLE
Chargepoint
E
Metal
Distribution
Board
Safevolt 50
SWA
CABLE
Figure 5
Non
SWA
CABLE
Chargepoint
E
Metal
Distribution
Board
SWA
CABLE
Non-Metal
Termination
Box
Safevolt 50
SWA
CABLE
SWA
CABLE
CityEV Safevolt® 50 User and Installation Manual