 SZ/IF

 Rated:  

SELV

Maximum number of sensors:  

10

Maximum number of valves:  

3

Max cable length from SZ/IF to last valve:  

30m (1.5mm

2

 cable)

Max cable length from SZ/IF to SZ/LFC:  

100m (1.5mm

2

 cable)

Power requirements:  

6v DC regulated mains adaptor (supplied with 

sensazone

)

Ingress Protection: 

IP54

 SZ/LFC

 Rated voltage:  

240VAC

Rated current:  

8A

Making capacity:  

16A for 1 second

Breaking capacity:  

4000VA

Max wire size:  

2.5mmsq

Ingress Protection: 

IP54

Circuits must have overload/fault protection of 10A or less.
Circuit protection and wire size must meet local wiring regulations.

NB:

 Rated Current is for a resistive load - when using inductive/capacitive loads such as fl uorescent ballasts, please 

derate the load to ensure the inrush current does not exceed the contact making capacity.

Warning:

 This is a functional switching device, and must not be used for safety or maintenance isolation.

Warning:

 This device is intended for use with hazardous voltages. The installation and maintenance of this device must 

be carried out by a qualifi ed electrician in accordance with local wiring regulations. Before installing this device, please 
read these installation instructions carefully.

 SZ/ASK

 Control classifi cation:  

Independent

Maximum load:  

3 x 2W 0.33A (6VDC) EMC emissions tested at load

Rated temperature range:  

0-40 deg C

Action classifi cation:  

Type 1.Y

Pollution classifi cation:  

Degree 1

Ingress protection:  

IP55 or IP65 (with respect to room when smooth, 

 

non-porous ceiling tile used)

 factory settings

 Range:  

~2.2m high x 5m diameter

Sensitivity setting:  

Medium

Hygiene rinse:  

On (30 min every 12 hours)

Run-on time:  

15 minutes

Additional fan run-on time:  

Off (Default)

15mm & 22mm valves:  

Max pressure 6 bar  

Min pressure (dynamic) 0.5 bar

1” and 1.25” valves:  

Max pressure 5 bar  

Min pressure (dynamic) 0.5 bar

 Ambient Temperature Range:  

Operating 0 to +40°C            

Storage -25 to +40°C

 LED indication on SZ/LFC (isolate mains supply to lights and fans before removing cover to 
reveal status LED)

Constant Green 

System idle and OK

1 green fl ash per second 

Fan on

2 green fl ash per second 

Fans and lights on

1 red fl ash per second 

Low supply voltage  

(Check wiring and contact Cistermiser)

2 red fl ashes per second 

Comms failure  

(Check wiring and contact Cistermiser)

LED indication on SZ/IF:

Constant green 

System idle and OK

1 green fl ash per second 

Valves open/lights on/fans on

Red fl ash 

Fault 

(Check wiring and contact Cistermiser)

 Usage advice and specifi cation

Summary of Contents for sensazone SZ/ASK

Page 1: ...rface Module A sensazone Light and Fan Control 3 To control the water supply to multiple areas of a washroom simultaneously Examples include a washroom divided into different areas and a washroom with two or more entrances sensazone core product A sensazone Interface Module Additional Sensor Kits Additional Valve Kits where applicable to a maximum of 3 valves per system 4 To control the water supp...

Page 2: ...adaptor 7 2 x universal fixing plug 8 2 x 6 x 1 1 2 screws 9 4 x 4 x 1 2 screws 10 4 x sticky pads 11 Extension cable to mains power adaptor 1 25m 12 Extension cable to solenoid valve 3m 1 sensazone Interface module 2 Sticky Pads x 2 3 Infrared Control Unit ICU 1 1 Solenoid valve either 15mm 22mm 1 or 11 4 Only supplied with 15mm or 22mm 2 2 3 4 5 6 7 8 9 10 11 12 3 2 0118 969 1611 sales cistermis...

Page 3: ...or 22mm 4 5 Additional Sensor Kit supplied parts 1 Sensor assembly consisting of sensor unit and backplate 2 2 x universal fixing plug 3 2 x 6 x 1 1 2 screws 4 4 x sticky pads 5 Extension Y Cable 1 4 2 3 sensazone Light and Fan Control SZ LFC supplied parts 1 sensazone Light Fan Control 2 Screws x 2 3 Fixings x 2 4 Sticky Pads x 4 1 2 4 5 3 0118 969 1611 sales cistermiser co uk www cistermiser co ...

Page 4: ... in the common entrance the water lights and fans will be activated in all areas of the washroom Example layout for single common entrance Scenario 1 and 2 Example layout for multiple entrances Scenario 3 and Scenario 4 When occupancy is detected at one of the entrances the water lights and fans will be activated in all areas of the washroom DOOR MINIMUM 1 METRE MINIMUM 1 METRE 4 0118 969 1611 sal...

Page 5: ... Grey or rainwater supply to washroom Grey or rainwater supply to washroom Max 3 metres cable length from sensor to power supply Max 100 metre cable length between SZ IF B and SZ LFC D Max 1 85 metres cable length CEILING A A C C E E D B Detection Zone 5 metres Detection Zone 5 metres 2 2 metres 2 2 metres 5 0118 969 1611 sales cistermiser co uk www cistermiser co uk Sensor s installation Refer to...

Page 6: ...and SZ LFC D Sensor s installation Refer to page 7 for details SZ IF installation Refer to page 7 for details SZ LFC installation Refer to page 8 for details Valve installation Refer to page 8 for details Mains power adapter Refer to page 9 for details A B D C E Cold water supply to washroom Cold water supply to washroom Isolating Valve not supplied Isolating Valve not supplied Hot water supply to...

Page 7: ...o go out of the same exit ensure that the wire is routed around the sensor as shown in the diagram below 6 Secure sensor unit to base plate and twist clockwise to lock into position SZ IF Installation Position the sensazone Interface Module SZ IF in accordance with the following 1 The cable length from the SZ IF to the furthest valve must NOT exceed 30m 2 The cable length from the SZ IF to the SZ ...

Page 8: ...ot exceed 8A 4 Connect the live feed for the fans to the FAN contactor Ensure load does not exceed 8A 5 Replace lid with screws provided before restoring power WARNING This is a functional switching device and must not be used for safety or maintenance isolation WARNING This device is intended for use with hazardous voltages The installation and maintenance of this device must be carried out by a ...

Page 9: ... co uk www cistermiser co uk 4 Testing and commissioning start up operation When the sensazone is powered up the LED will be a constant amber for up to 15 seconds after which it will flash amber for 5 seconds The water supply ies into the washroom will now be on for the default run on time of 15 minutes The default run on time can be changed to 30 minutes See the ICU guide in section 7 normal oper...

Page 10: ...device please read these installation instructions carefully SZ ASK Control classification Independent Maximum load 3 x 2W 0 33A 6VDC EMC emissions tested at load Rated temperature range 0 40 deg C Action classification Type 1 Y Pollution classification Degree 1 Ingress protection IP55 or IP65 with respect to room when smooth non porous ceiling tile used factory settings Range 2 2m high x 5m diame...

Page 11: ...5 Component dimensions 134mm 101mm 93mm 130mm 125mm 93mm 93mm 124mm 1 valve 11 4 valve 15mm or 22mm valve 76mm 41mm 82mm 31mm 148mm 11 0118 969 1611 sales cistermiser co uk www cistermiser co uk ...

Page 12: ...nutes Option 2 Run on time adjustment 30 minutes Sequence of programme once option has been selected Wait for single green flashing LED Wait for double green flashing LED Once your option has been chosen the LED will be constant green for 5 seconds Cup your hand over the sensor for 2 seconds to select this option The LED will be constant green for 5 seconds Cup your hand over the sensor for 2 seco...

Page 13: ...figuring sensor sensitivity range Enter into configuration mode Point the ICU at the sensazone and press the 1 the sensor blinks green once Decrease or increase the sensor range by pressing the and buttons respectively The sensor blinks green every time or is pressed and blinks red when the minimum or maximum value is reached Press button to verify the sensor sensitivity setting the sensor display...

Page 14: ...ttons respectively The sensor blinks green every time or is pressed and blinks red when the minimum or maximum value is reached Press button to verify the sensor light threshold setting the sensor displays the current setting by flashing green Single flash minimum sensitivity setting Double flash medium sensitivity setting Triple flash maximum sensitivity setting Save setting and exit ICU configur...

Page 15: ... have not been exceeded There is water in one zone but not all zones Ensure water pressure does not exceed the maximum working pressure of the valve water at outlets at all times Sensor LED not lit Check electrical power supply to the sensor and all electrical connections to the valve If electrical power confirmed please contact Cistermiser for further advice Valves not opening or closing when the...

Page 16: ...is faulty please either contact Cistermiser directly on 0118 969 1611 or at warranty cistermiser co uk with a photograph and the serial number to diagnose the cause of the problem The warranty on Cistermiser products can be extended within one year of date of manufacture at no cost to three years from the date of installation by completing the enclosed warranty card or at www cistermiser co uk war...

Reviews: