gray coloring). You can also order the 1200-W HVAC/HVDC power supply which has dual-direction airflow
with white coloring. Dual-direction airflow modules automatically use the airflow direction of the other
modules installed in the switch.
The fan and power supply modules are field replaceable and you can replace one fan module or one power
supply module during operations so long as the other modules are installed and operating. If you have only
one power supply installed, you can install the replacement power supply in the open slot before removing
the original power supply.
All of the fan and power supply modules must have the same direction of airflow. Otherwise, the switch
can overheat and shut down. If you are installing a dual-direction power supply, that module will
automatically use the same airflow direction as the other modules in the switch.
Note
If the switch has port-side intake airflow (burgundy coloring for fan modules), you must locate the ports
in the cold aisle. If the switch has port-side exhaust airflow (blue coloring for fan modules), you must
locate the ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut
down.