Figure 9: Attaching a Left Cable Management Assembly to a Rack-Mount Bracket
Position the assembly so that the two upper hooks on the rack-mount bracket
fit inside the two holes on the assembly, and then slide the assembly down so
that it is held by the hooks.
3
Rack-mount bracket.
1
Loosely fasten the assembly to the rack-mount bracket with four M4x10
screws. Do not tighten these screws.
4
Upper cable management
assembly.
2
Step 4
Repeat Step 3 to attach an upper cable management assembly to the upper right side of the chassis. When completed,
the chassis will appear as shown in
Figure 10: Cable Management Assemblies Attached to the Rack-Mount Brackets,
.
Installing a Cisco Nexus 7018 Chassis
19
Installing a Cisco Nexus 7018 Chassis
Installing the Cable Management Frame