Revised: April 13, 2018,
Connect AC Power to NCS 1001
NCS 1001 relies on the protective devices in the building installation to protect against short circuit,
overcurrent, and ground faults. Ensure that the protective devices comply with local and national electrical
codes.
Caution
The voltage rating value for AC power ranges either between 200 V to 240 V or between 100 V to 127 V depending on the standards
in various countries.
A dual pole breaker is needed for the installation. The rating of the dual pole breaker is 16A for International
and 20A for USA and Canada.
Note
Figure 22: Hot Area on PSU Faceplate
Procedure
Step 1
Verify that the AC cable is installed in the correct AC source panel. Ensure that either the fuse is removed or the circuit
breaker is in the off position and locked out.
For an AC power supply, fuse or breaker rating must not exceed
20A.
Note
32