For
n
+1 redundancy, you can use one or two power sources for the two power supplies. For
n
+
n
redundancy,
you must use two power sources and connect each power supply to a separate power source.
Note
The power supplies are rated to output up to 1100 W, but the switch requires less than those amounts of power
from the power supply. To operate the switch, you must provision enough power from the power source to
cover the requirements of both the switch and a power supply. Typically, this switch and a power supply
require about 367 W of power input from the power source, but you must provision as much as 777 W power
input from the power source to cover peak demand.
Some of the power supply modules have rating capabilities that exceed the switch requirements. When
calculating your power requirements, use the switch requirements to determine the amount of power that is
required for the power supplies.
Note
To minimize the possibility of circuit failure, make sure that each power-source circuit that is used by the
switch is dedicated to the switch.
For AC input application, please refer to the following statement:
Note
Statement 1005—
Circuit Breaker
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that the
protective devices are rated not greater than 20A (North America), 16A (Europe), and 13A (UK).
Warning
For DC input application, please refer to the following statement:
Note
Statement 1005—
Circuit Breaker
This product relies on the building's installation for short-circuit (overcurrent) protection.
• Ensure that the protective devices are rated not greater than 30A when the switch is powered with regular
DC power supplies (rated 48-60VDC).
• Ensure that the protective devices are rated not greater than 10A when the switch is powered with HVDC
power supplies (rated 240-350VDC).
Warning
Statement 1033
Connect the unit only to DC power source that complies with the Safety Extra-Low Voltage (SELV)
requirements in IEC 60950 based safety standards.
Warning
Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide
8
Preparing the Site
Planning for Power Requirements