15
Cisco 10005 ESR DC Power Entry Module Installation
78-12653-01
Adding or Replacing a DC PEM
Step 3
Insert the end of the grounding wire into the grounding receptacle, which is the
bottom receptacle in the terminal block on the PEM (
Figure 6
).
Figure 6
Insert Grounding Wire into Grounding Receptacle
Step 4
Ensure that no copper wire strands are left outside the receptacle.
Step 5
Use the screwdriver to tighten the ground screw in the terminal block to a torque
of 1.5 to 1.8 newton meters (13.28 to 15.93 inch-pounds). (Tighten in a clockwise
direction.) To avoid breaking the screw, do no exceed 2.3 newton meters.
Step 6
Pull on the wire to ensure that it is held firmly in place.
Step 7
Make sure that the other end of the wire is connected to ground at the DC power
source.
Step 8
If you are connecting two power sources to the Cisco 10005 ESR, repeat this
procedure for the second PEM.
CAUTION:
USE COPPER CONDUCT
ORS ONL
Y
ATTENTION:
N'UTILISEZ Q
UE DES CONDUCTEURS EN CUR
VE
CAUTION:
TERMINALS MA
Y BE ENERGIZED
. TURN OFF PO
WER SOURCE CIRCUIT
BREAKER AND REMO
VE PO
WERSUPPL
Y BEFORE A
CCESSING
TERMINALS
.
GML
POWER
FAULT
THIS UNIT HAS MORE
THAN ONE PO
WER
SUPPL
Y CORD
. DISCONNECT
TWO (2)
POWER SUPPL
Y CORDS BEFORE
SERVICING
TO AVOID ELECTRIC SHOCK.
CAUTION
CAUTION:
USE COPPER CONDUCT
ORS ONL
Y
ATTENTION:
N'UTILISEZ Q
UE DES CONDUCTEURS EN CUR
VE
CAUTION:
TERMINALS MA
Y BE ENERGIZED
. TURN OFF PO
WER SOURCE CIRCUIT
BREAKER AND REMO
VE PO
WERSUPPL
Y BEFORE A
CCESSING
TERMINALS
.
GML
MISWIRE
THIS UNIT HAS MORE
THAN ONE PO
WER
SUPPL
Y CORD
. DISCONNECT
TWO (2)
POWER SUPPL
Y CORDS BEFORE
SERVICING
TO AVOID ELECTRIC SHOCK.
CAUTION
53627
INPUT
-48/60 V
35A