Connecting DC Power to IW-6300H-DC-x-K9
This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the
protective device is rated not greater than:5 A. Statement 1005
Warning
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. Statement 1022
Warning
To reduce risk of electric shock, connect the unit only to DC power source that complies with the Safety
Extra-Low Voltage (SELV) requirements in IEC 60950 based safety standards or ES1 requirements in IEC
62368 based safety standards. Statement 1033
Warning
To route and connect the power cable to the IW-6300H-DC-x–K9 model, follow these steps:
Procedure
Step 1
Open the access point cover. See
Opening the Access Cover, on page 13
for instructions.
Step 2
Ensure a 6 AWG ground wire is connected to the access point (see
Grounding the Access Point , on page 19
Step 3
Route the power cable through the 1/2-NPT port.
Figure 18: Connecting Internal Ground and DC Power for IW-6300H-DC-x-K9
Internal ground
2
Terminal block
1
Step 4
Use a wire stripper tool to remove the insulation from each wire. Remove only enough wire to provide adequate
crimp on to ring terminals (Cisco supplied).